4

If you have a single stage compressor system see the dia-
gram below. A relay (customer provided) should be installed 
as shown in Fig 7 to switch the fan speed to the next lower 
speed on a call for dehumidification from the thermostat. The 
reduction in air flow allows the coil to remove more humidity 
from the air. The relay should be rated for blower motor load. 
Since this configuration reduces the air flow in cooling, the 

WIRING DIAGRAMS 

anti-freeze-up control (White-Rodgers CAFC) or equivalent is 
recommended. The CAFC prevents the air conditioning coil 
from freezing due to low air flow, dirty filters, low refrigerant 
pressure, etc. The CAFC snaps onto the suction line close to 
the evaporator coil as possible and breaks the compressor 
circuit when the suction line drops below 38 °F and re-make 
the circuit at 46°F.

HOT

NEUTRAL

120 VAC

24 VAC

Relay
90-290Q
or equivalent 

HOT

NEUTRAL 120 VAC

TRANSFORMER

R

HM

Humidifier 

System

Figure 6 – Typical Wiring for 120V Humidifier System

HOT

NEUTRAL 120 VAC

TRANSFORMER

HM

24 VAC

Humidifier 

System

R

Figure 7 – Typical Wiring for 24V Humidifier System

Dehumidification wiring without an electronically controlled variable speed blower system for 

single stage compressor system only. 

HM

DHM

Humidification Terminal, 

Energizes on call for 

heat if Humidity setpoint 

is above room humidity. 

Can also be used to 

provide humidification 

independent of a call for 

heat and/or in cooling 

mode if Automatic 

Humidification is 

selected in Configura-

tion Menu item #34

De-energizes on call for 

Dehumidification to 

lower the fan speed. 

The DHM terminal is 

only used on systems 

with a compatible 

dehumidification feature 

that have the required 

terminal connection on 

the contol module or 

have a relay installed to 

lower the fan speed

+

S

-

Supply voltage 

to remote 

temperature

sensor

Remote 

temperature 

sensor signal

Supply voltage 

to remote 

temperature

sensor

Figure 4 – Humidity and Sensors

 Relay 
90-293Q 
or equivalent

No

NC

“Heat Fan Output”

N

Dehum

Speed Fan

Med

DHM

N

Low

Normal High

“Cool Fan Output”

1

2

Normal Cool speed position (DHM energized)
Dehum speed mode (DHM de-energized)

1

2

Figure 5 – Typical Wiring for Dehumidifier System

Содержание 1F95-1291

Страница 1: ...ury However this prod uct may replace a product that contains mercury Mercury and products containing mercury must not be discarded in household trash Do not touch any spilled mercury Wearing non absorbent gloves clean up any spilled mercury and place in a sealed container For proper disposal of a product containing mercury or a sealed container of spilled mercury place it in a suitable shipping c...

Страница 2: ...e Power Stealing Switches Fig 1 should be left in the On position for most systems The information in the following table details the thermostat power method and switch options WARNING Thermostat installation and all components of the control system shall conform to Class II circuits per the NEC code INSTALLATION Figure 1 Thermostat Base Multi Stage 1F95 1291 2 AA Batteries Power Stealing Switches...

Страница 3: ...ency Mode 1st stage Note Dual Fuel option de energizes Heat mode stage 1 compressor when auxiliary heat is energized Heat mode 3rd stage Emergency Mode 1st stage Note Dual Fuel option de energizes Heat mode stages 1 and 2 both compressors when auxiliary heat is energized Heat mode 4th stage Emergency Mode 2nd stage Note Dual Fuel option de energizes Heat mode stages 1 and 2 both compressors when a...

Страница 4: ...tem HOT NEUTRAL 120 VAC TRANSFORMER HM 24 VAC Humidifier System R Figure 7 Typical Wiring for 24V Humidifier System Dehumidification wiring without an electronically controlled variable speed blower system for single stage compressor system only HM DHM Humidification Terminal Energizes on call for heat if Humidity setpoint is above room humidity Can also be used to provide humidification independe...

Страница 5: ... 3 7 3 8 3 9 3 20 21 2 1 11 12 10 16 17 9 8 18 14 13 4 19 15 A steady Cool Savings display indicates the feature is enabled in the installer menu A flashing Cool Savings display indicates the feature is active 16 Remote indicates that the indoor remote temperature sensor is being accessed Outdoor Remote indi cates the outdoor remote temperature sensor is being accessed 17 Display time remote tempe...

Страница 6: ... available if 4 is 0 8 FA Heat Cr SL Selects Adjustable Anticipation cycle rate Heat 9 FA Cool Cr SL Selects Adjustable Anticipation cycle rate Cool 10 FA Cr AU Em SL Selects Adjustable Anticipation cycle rate auxiliary This item is only to appear if HP1 or HP2 is selected above 11 OFF CL On Selects Compressor Lockout 12 On dL OFF Selects Continuous Display backlight 13 0 Temperature 5 LO to 5 HI ...

Страница 7: ...h the program setpoint at the time you specify Example The heating program is 65 F at night and 70 at 7 AM If the building temperature is 65 F the difference is 5 F Allowing 5 minutes per F rise the thermostat set point will change to 70 at 6 35 AM Cooling allows more time per F because it takes longer to reach temperature 8 9 10 Cycle Rate Selection The factory default setting is fast cycle FA Cr...

Страница 8: ... to 6 When an offset starts or is active Cool Savings will flash on the display The principle of this energy saving feature takes advantage of the long air conditioning run times lowering the indoor humidity allowing a slightly higher temperature to feel comfortable As the peak load subsides this feature also takes advantage of the air conditioner s increased capacity under more efficient conditio...

Страница 9: ... stage separation This adjust ment allows a small change in the operation of your heat INSTALLER CONFIGURATION MENU pump system versus your auxiliary system relative to the thermostat adjustment The higher the number the sooner the auxiliary stage energizes for better comfort The lower the number the longer period of time before auxiliary is energized for more economy Note This setting is not minu...

Страница 10: ...ded maintenance schedule When Change UV Lamp is displayed you can clear it by pressing Clean Display 46 47 Change Humidifier Pad This feature allows the thermostat to display the words Change Pad after a set time of humidifier operation This is a reminder to main tain or clean your humidifier The factory set interval for Change Pad to be displayed is 100 hours of humidifier operation This should b...

Страница 11: ... and or property damage if the outdoor temperature is below 50 F DO NOT operate the cooling system CAUTION Fan On selection runs the fan continuously for increased air circulation or to allow additional air cleaning Tip Running the fan more frequently will increase your energy consumption Most systems use a 1 2 or 1 3 HP electric motor to power the fan Choose the System Setting Cool Off Heat Em Au...

Страница 12: ...u wish to copy to is flashing 5 Press Copy Copy will disappear the day you copied from will disappear and the day s you copied to will be on 6 If you wish to copy this same program into other days press Copy and repeat steps 3 4 and 5 7 Press Run Schedule to return to normal operation Fill in the blank schedule on the next page then Enter the Heating Program 1 Press the Menu key and then press Set...

Страница 13: ...of the week You can eliminate these two program periods in the configuration menu reference 5 if the building is occupied all day Day period will change to 6 00 AM and 70 and can be programmed as required Wake Up Morning Leave For Work Day Return Home Evening Go To Bed Night Heating Program 6 00 AM 70 F 8 00 AM 62 F 5 00 PM 70 F 10 00 PM 62 F Cooling Program 6 00 AM 75 F 8 00 AM 83 F 5 00 PM 75 F ...

Страница 14: ...n the terminal block allow connection of the remote sensor The thermostat must have 24 VAC Common connection to terminal C for the remote sensor to operate The remote sen sor can be enabled or disabled in the Installer Configuration menu item 29 When remote sensor Remote is selected Off factory de fault no remote sensor is enabled When remote sensor is selected On the next step is to select the re...

Страница 15: ... the dual fuel temperature setpoint menu item 33 can be set to a temperature of 5 through 50 When outdoor remote sensor is not installed a software logic based dual fuel number menu item 34 from 01 to 09 can be selected A higher temperature or dual fuel setting will provide a smaller stage separation between the heat pump and Aux to give more comfort A lower temperature or number will provide a la...

Страница 16: ... connection to verify they are not shorted or touching together No bare wire should stick out from under terminal block Try resetting the thermostat as de scribed above If the condition persists the manufacturer of your system or service person can instruct you on how to test the Heat Cool system for correct operation If the system operates correctly replace the thermostat Thermostat Setting Therm...

Отзывы: