Temperature Probes:

NTC

The control is shipped with an NTC (Negative Temperature 
Coefficient) sensor, with a cable length of 7½ feet. Cable 
length can be extended up to 400 feet by appropriately splic-
ing and adding additional cable (22 AWG or larger diameter) 

PTC

The control may be connected to an existing PTC (Positive 
Temperature Coefficient) sensor. Make sure the PTC sensor 
meets the specifications tables below. Failure to do so will 
result in temperature inaccuracies. The PTC input may not be 

NTC TEMPERATURE VERSUS RESISTANCE TABLES

PTC TEMPERATURE VERSUS RESISTANCE TABLES

as needed – polarity is not important. When extending cable 
length, verify temperature accuracy and use the menu Ambi-
ent Temperature Offset (OFS) settings to compensate accord-
ingly if required.

extended more than 50 feet, and the wire gauge should be 
18 AWG wire or larger diameter. Be sure the probe attached 
matches the resistance vs. temperature tables or temperature 
inaccuracies may occur.

SPECIFICATIONS 

Temperature

 (°F)        (°C)

Resistance

(K

)

-40

-40

328.29

-31

-35

236.83

-22

-30

172.90

-13

-25

127.65

-4

-20

95.23

5

-15

71.74

14

-10

54.56

23

-5

41.85

32

0

32.37

41

5

25.23

Temperature

(°F)         (°C)

Resistance

(K

)

50

10

19.82

59

15

15.67

68

20

12.48

77

25

10.00

86

30

8.07

95

35

6.55

104

40

5.34

113

45

4.38

122

50

3.61

131

55

2.99

Temperature

(°F)        (°C)

Resistance

(K

)

140

60

2.49

149

65

2.09

158

70

1.76

167

75

1.48

176

80

1.26

185

85

1.07

194

90

0.92

203

95

0.79

212

100

0.68

221

105

0.59

Temperature

 (°F)        (°C)

Resistance

(K

)

-40

-40

613

-31

-35

640

-22

-30

668

-13

-25

697

-4

-20

727

5

-15

758

14

-10

789

23

-5

822

32

0

855

41

5

889

Temperature

(°F)         (°C)

Resistance

(K

)

50

10

924

59

15

960

68

20

997

77

25

1035

86

30

1074

95

35

1113

104

40

1153

113

45

1194

122

50

1236

131

55

1279

Temperature

(°F)        (°C)

Resistance

(K

)

140

60

1323

149

65

1368

158

70

1413

167

75

1459

176

80

1506

185

85

1554

194

90

1602

203

95

1652

212

100

1702

221

105

1753

Load Output Relay:  

 

Ratings (Maximum):

 

120VAC  208VAC  240VAC

Full Load Amps NC & Load 

16 A 

9.2 A 

8 A

Locked Rotor Amps NC & Load 

96 A 

55.2 A  48 A

Non-Inductive Amps NC & Load 

16 A 

16 A 

16 A

Horsepower NC & Load 

 

1 hp 

1 hp 

1 hp

24 VAC NC & Load 

100 VA, 30 VAC Max (Class 2)

Pilot Duty NC & Load 

125 VA, 24 to 240 VAC

•  Minimum Load Rating: 1 Amp @ 24 VAC  
•  Note: the above minimum current/voltage is specified 
   to assure proper operation.

NOTE: 

For use on single phase circuits only.

Alarm Relay Ratings

 (Maximum):   

N.O. contact: 1 Amp, 5 to 24 V, AC or DC

Operating Ambient Ratings (Control Enclosure):

Operating Temperature: 

-29°F to 140°F (-34° to 60°C)

Storage Shipping Ambient Ratings:

Storage Temperature: 

-40°F to 185°F (-40° to 85°C)

Operating Humidity: 

0 to 95% Relative Humidity, 

 

                             Non-Condensing

Maximum Dew Point:  

85°F (29°C)

Temperature Set-Point Range:

Set-Point Range:  -40° to 220°F (-40° to 104°C)
Differential Range: 

1 to 30 (Degrees F or Degrees C)

Case:

NEMA 1 Enclosure, Flammability Rating: UL94VO

Содержание 16E09-101

Страница 1: ...applications which range from refrigeration to heating due to the wide temperature range of the control stated above Typical applications include walk in freezers beverage coolers supermarket display cases for flowers produce meats convenience store refrigerated cases food warmers boiler control and certain industrial applications Save these instructions for future use WARNING 16E09 101 Optional A...

Страница 2: ...E REFER TO PAGE 6 STATUS INDICATOR LED LIT WHEN CONTROLLED LOAD IS ENERGIZED ON SEE NOTE TEMPERATURE UP BUTTON TEMPERATURE DOWN BUTTON MENU BUTTON PRESS TO ENTER MENU MODE REFER TO PAGES 4 5 SW1 Refrigeration Cool Heating Heat Switch SW1 must be set for system mode as shown To prevent electrical shock and or equipment dam age disconnect electric power to system at main fuse or circuit breaker box ...

Страница 3: ... optional connection to customer alarm equipment Binary Input Gold Plated Contacts 24 VAC Block not used TH Thermostat Hot TR Thermostat Return NTC Temperature Sensor PTC Temperature Sensor Fig 3 Line Voltage Application Power Stealing 120 VAC Hot Neutral L1 L2 208 240 VAC Voltage Input Load Power Stealing Power Stealing is an electronic design within the control that can eliminate the need to con...

Страница 4: ...s how the set point temperature will operate the load terminal CI indicates the setpoint temperature will be the Cut In temperature CO indicates the temperature will be the Cut Out temperature See Operation section SOF Sensor Operation Failure Cool Heat 1 0 0 or 1 None Cooling Selects the operation of the Control Load relay in the event of a sensor failure in Cool mode 1 default will cause the loa...

Страница 5: ...l Set Point SP Cut In Differential 5 Setpoint temperature 40 Temperature Range 40 Setpoint Cut Out 45 SW1 Cool Set Point SP Cut Out Differential 5 Setpoint temperature 40 Temperature Range HEAT To use as a Heating control SW1 must be set to Heat The flame icon will display If control is in Heat mode and Set Point is selected as the Cut Out Temperature Operating Setpoint Differential Range Temperat...

Страница 6: ... should be given to these events to prevent a false alarm If the control set back feature is used to change the setpoint the delay period set in AL should consider the time it takes for the system to reach the set back temperature to avoid a false alarm Power Loss If the temperature control experiences an input power failure the control will close the alarm relay before total power of the control ...

Страница 7: ...Resistance KΩ 140 60 2 49 149 65 2 09 158 70 1 76 167 75 1 48 176 80 1 26 185 85 1 07 194 90 0 92 203 95 0 79 212 100 0 68 221 105 0 59 Temperature F C Resistance KΩ 40 40 613 31 35 640 22 30 668 13 25 697 4 20 727 5 15 758 14 10 789 23 5 822 32 0 855 41 5 889 Temperature F C Resistance KΩ 50 10 924 59 15 960 68 20 997 77 25 1035 86 30 1074 95 35 1113 104 40 1153 113 45 1194 122 50 1236 131 55 127...

Страница 8: ... line 1 888 725 9797 www white rodgers com www emerson com White Rodgers is a division of Emerson Electric Co The Emerson logo is a trademark and service mark of Emerson Electric Co TROUBLESHOOTING Temperature differential is wider than set Temperature change of customer s unit is fast and the Anti Short Cycle delay setting may be overriding the call to activate the heat or cool Solution lower Ant...

Страница 9: ... descongelación o cualquier otro dispositivo con la función de alarma activada Esto produciría una falsa alarma Si la función de alarma está activada conecte según el diagrama de Non Power Stealing El diferencial de temperatura es más amplio que el ajustado El cambio de temperatura de la unidad del cliente es rápido y el ajuste de demora anti ciclo corto podría estar anulando la llamada para activ...

Страница 10: ... DE TEMPERATURA VS RESISTENCIA PTC según sea necesario La polaridad no es importante Si ex tiende la longitud del cable verifique que la temperatura sea precisa y utilice los ajustes de compensación de temperatura ambiente OFS del menú para compensarla en caso de que sea necesario más de 50 pies y el cable deberá tener un calibre de 18 AWG o un diámetro más grande Asegúrese de que la sonda conecta...

Страница 11: ...rio cambie la opción de menú LP a On Al salir del menú cuando se guarden los ajustes las teclas o y quedarán desactivadas del uso normal Para desbloquear el teclado presione y manténgalo presionado durante 5 segundos La pantalla cambiará y mostrará LP On Presione o por un momento para cambiar el ajuste a Off y luego presione durante algunos instantes El control volverá a su funcionamiento normal y...

Страница 12: ...la temperatura de referencia se selecciona como temperatura de desconexión Rango operativo de Temperatura Diferencial temperatura de referencia más Ejemplo 40 Temperatura de referencia Temperatura de desconexión 45 SW1 Enfriamiento Temperatura de referencia SP Temperatura de desconexión Diferencial 5 Temperatura de referencia 40 Rango de temperatura CALOR HEAT Para usar como control de calefacción...

Страница 13: ...ado Off On u Off del panel frontal OFS Compensación de 0 4 3 2 1 0 temperatura ambiente 1 2 3 4 Opción Ajuste Opciones del de Presione o menú Descripción fábrica para seleccionar Observaciones Enfriamiento Selecciona el funcionamiento del relé de carga de control en caso de una falla del sensor en el modo Frío 1 ajuste predeterminado hace que los contactos de carga del relé se cierren y si el sens...

Страница 14: ...e alarma Para la conexión opcional al equipo de alarma del cliente NTC Coeficiente de temperatura negativo PTC Coeficiente de temperatura positivo NOTA Sólo es posible conectar un sensor PTC o NTC El sensor debe cumplir con las especificaciones de temperatura vs resistencia indicadas Power Stealing Power Stealing es una característica electrónica del control que elimina la necesidad de conectar un...

Страница 15: ...6 LED INDICADOR DE ESTADO SE ENCIENDE CUANDO LA CARGA CONTROLADA ESTÁ ENERGIZADA ON VEA LA NOTA BOTÓN DE INCREMENTO DE TEMPERATURA BOTÓN DE REDUCCIÓN DE TEMPERATURA BOTÓN DE MENÚ PRESIONE PARA INGRESAR EN EL MODO DE MENÚ REFIÉRASE A LAS PÁGINAS 4 Y 5 SW1 Enfriamiento Cool Calefacción Heat El interruptor SW1 debe ajustarse para el modo de funcionamiento del sistema como muestra la figura Para evita...

Страница 16: ...ras carnes en super mercados exhibidores refrigerados en tiendas de conveniencia calentadores de comida control de calefactor y ciertas aplica ciones industriales ADVERTENCIA Lea y siga con atención todas las instrucciones antes de instalar o utilizar este control para evitar lesiones personales y o daños materiales Para evitar descargas eléctricas lesiones personales y o daños al equipo desconect...

Отзывы: