LCD display, display back-light and green status indica-
tor LED turn off in Power Stealing mode:

This “off” condition is normal for the control in power stealing 
mode when wired with a defrost timer or other device that 
interrupts electrical power to the control.  
No control settings will be lost during this time, however, the 
installer must ensure that applications requiring power steal-
ing are suitable for the control to be off during these periods.
Please note: if the built-in alarm feature of the control is to 
be used on systems that may interrupt power to the control, 
the control must be wired with a neutral wire and set in non-
power stealing mode. This will keep the control continuously 
powered unless there is an actual power interruption or loss. 
In this case, the control will be able to signal an alarm for 
system power loss.

Display indicates “CaL” on power up.

Control was not calibrated. Return control for replacement.

Unit does not turn on, (LCD does not display anything):

-  Check that wiring is correct.
-  Make sure power is turned on.
-  Check that wiring is under terminal blocks correctly.
-  Make sure both switches inside control are set to proper 
  position.
-  If in Power Steal mode,
  -  Make sure the load draws a minimum of 2.5 amp AC. If 
    not, wire per the Non-Power Stealing diagram.
  -  Make sure nothing "breaks/opens the load line, such as
    a defrost timer or any other device, with the alarm
    feature enabled. This would cause a false alarm. If the
    alarm function is enabled, wire per the Non-Power
    Stealing diagram.

TECH SUPPORT HELP LINE: 1-888-725-9797 

www.white-rodgers.com

www. emerson.com

White-Rodgers is a division
of Emerson Electric Co.

The Emerson logo is a
trademark and service mark
of Emerson Electric Co.

TROUBLESHOOTING 

Temperature differential is wider than set:

-  Temperature change of customer's unit is fast, and the  
  Anti Short Cycle delay setting may be overriding the “call”  
  to activate the heat or cool. Solution – lower Anti Short  
  Cycle delay.

Installation and Power Up:

False alarm sounds, temperature has not yet reached set-
point setting. CUSTOMER must disable alarm (AL = 0), until 
setpoint temperature is reached, then set alarm delay time.

Customer Changes Setpoint Temperature:

False alarm sounds. CUSTOMER must disable alarm 
(AL = 0), while unit is adjusting to new temperature. CUS-
TOMER must then set the alarm delay time when tempera-
ture is reached.

Bin/Set Back

False alarm sounds. CUSTOMER must set the delay time 
with sufficient delay time to assure the Set Back temperature 
is reached before the alarm delay time has expired.
Note: If the Set Back temperature cannot be reached within 
99 minutes (the maximum Alarm delay time), change the 
Set Back value to a lower number of degrees. If a lower set 
back can not be used, you may not be able to use the alarm 
feature.

Alarm Sounds, Reason Unknown:

CUSTOMER should make sure the Alarm (AL) delay time is 
great enough to cover other conditions when the unit tem-
perature may not be able to stay within 5 degrees.
-  Loading or unloading of stock and the doors are open.
  (Add sufficient delay time to the alarm delay).
-  Power is lost to the control if the line is broken/open by a
  defrost timer or other device. (Wire control per the Non
  Power Stealing line voltage schematic and connect/add
  a neutral line connection).

Содержание 16E09-101

Страница 1: ...applications which range from refrigeration to heating due to the wide temperature range of the control stated above Typical applications include walk in freezers beverage coolers supermarket display cases for flowers produce meats convenience store refrigerated cases food warmers boiler control and certain industrial applications Save these instructions for future use WARNING 16E09 101 Optional A...

Страница 2: ...E REFER TO PAGE 6 STATUS INDICATOR LED LIT WHEN CONTROLLED LOAD IS ENERGIZED ON SEE NOTE TEMPERATURE UP BUTTON TEMPERATURE DOWN BUTTON MENU BUTTON PRESS TO ENTER MENU MODE REFER TO PAGES 4 5 SW1 Refrigeration Cool Heating Heat Switch SW1 must be set for system mode as shown To prevent electrical shock and or equipment dam age disconnect electric power to system at main fuse or circuit breaker box ...

Страница 3: ... optional connection to customer alarm equipment Binary Input Gold Plated Contacts 24 VAC Block not used TH Thermostat Hot TR Thermostat Return NTC Temperature Sensor PTC Temperature Sensor Fig 3 Line Voltage Application Power Stealing 120 VAC Hot Neutral L1 L2 208 240 VAC Voltage Input Load Power Stealing Power Stealing is an electronic design within the control that can eliminate the need to con...

Страница 4: ...s how the set point temperature will operate the load terminal CI indicates the setpoint temperature will be the Cut In temperature CO indicates the temperature will be the Cut Out temperature See Operation section SOF Sensor Operation Failure Cool Heat 1 0 0 or 1 None Cooling Selects the operation of the Control Load relay in the event of a sensor failure in Cool mode 1 default will cause the loa...

Страница 5: ...l Set Point SP Cut In Differential 5 Setpoint temperature 40 Temperature Range 40 Setpoint Cut Out 45 SW1 Cool Set Point SP Cut Out Differential 5 Setpoint temperature 40 Temperature Range HEAT To use as a Heating control SW1 must be set to Heat The flame icon will display If control is in Heat mode and Set Point is selected as the Cut Out Temperature Operating Setpoint Differential Range Temperat...

Страница 6: ... should be given to these events to prevent a false alarm If the control set back feature is used to change the setpoint the delay period set in AL should consider the time it takes for the system to reach the set back temperature to avoid a false alarm Power Loss If the temperature control experiences an input power failure the control will close the alarm relay before total power of the control ...

Страница 7: ...Resistance KΩ 140 60 2 49 149 65 2 09 158 70 1 76 167 75 1 48 176 80 1 26 185 85 1 07 194 90 0 92 203 95 0 79 212 100 0 68 221 105 0 59 Temperature F C Resistance KΩ 40 40 613 31 35 640 22 30 668 13 25 697 4 20 727 5 15 758 14 10 789 23 5 822 32 0 855 41 5 889 Temperature F C Resistance KΩ 50 10 924 59 15 960 68 20 997 77 25 1035 86 30 1074 95 35 1113 104 40 1153 113 45 1194 122 50 1236 131 55 127...

Страница 8: ... line 1 888 725 9797 www white rodgers com www emerson com White Rodgers is a division of Emerson Electric Co The Emerson logo is a trademark and service mark of Emerson Electric Co TROUBLESHOOTING Temperature differential is wider than set Temperature change of customer s unit is fast and the Anti Short Cycle delay setting may be overriding the call to activate the heat or cool Solution lower Ant...

Страница 9: ... descongelación o cualquier otro dispositivo con la función de alarma activada Esto produciría una falsa alarma Si la función de alarma está activada conecte según el diagrama de Non Power Stealing El diferencial de temperatura es más amplio que el ajustado El cambio de temperatura de la unidad del cliente es rápido y el ajuste de demora anti ciclo corto podría estar anulando la llamada para activ...

Страница 10: ... DE TEMPERATURA VS RESISTENCIA PTC según sea necesario La polaridad no es importante Si ex tiende la longitud del cable verifique que la temperatura sea precisa y utilice los ajustes de compensación de temperatura ambiente OFS del menú para compensarla en caso de que sea necesario más de 50 pies y el cable deberá tener un calibre de 18 AWG o un diámetro más grande Asegúrese de que la sonda conecta...

Страница 11: ...rio cambie la opción de menú LP a On Al salir del menú cuando se guarden los ajustes las teclas o y quedarán desactivadas del uso normal Para desbloquear el teclado presione y manténgalo presionado durante 5 segundos La pantalla cambiará y mostrará LP On Presione o por un momento para cambiar el ajuste a Off y luego presione durante algunos instantes El control volverá a su funcionamiento normal y...

Страница 12: ...la temperatura de referencia se selecciona como temperatura de desconexión Rango operativo de Temperatura Diferencial temperatura de referencia más Ejemplo 40 Temperatura de referencia Temperatura de desconexión 45 SW1 Enfriamiento Temperatura de referencia SP Temperatura de desconexión Diferencial 5 Temperatura de referencia 40 Rango de temperatura CALOR HEAT Para usar como control de calefacción...

Страница 13: ...ado Off On u Off del panel frontal OFS Compensación de 0 4 3 2 1 0 temperatura ambiente 1 2 3 4 Opción Ajuste Opciones del de Presione o menú Descripción fábrica para seleccionar Observaciones Enfriamiento Selecciona el funcionamiento del relé de carga de control en caso de una falla del sensor en el modo Frío 1 ajuste predeterminado hace que los contactos de carga del relé se cierren y si el sens...

Страница 14: ...e alarma Para la conexión opcional al equipo de alarma del cliente NTC Coeficiente de temperatura negativo PTC Coeficiente de temperatura positivo NOTA Sólo es posible conectar un sensor PTC o NTC El sensor debe cumplir con las especificaciones de temperatura vs resistencia indicadas Power Stealing Power Stealing es una característica electrónica del control que elimina la necesidad de conectar un...

Страница 15: ...6 LED INDICADOR DE ESTADO SE ENCIENDE CUANDO LA CARGA CONTROLADA ESTÁ ENERGIZADA ON VEA LA NOTA BOTÓN DE INCREMENTO DE TEMPERATURA BOTÓN DE REDUCCIÓN DE TEMPERATURA BOTÓN DE MENÚ PRESIONE PARA INGRESAR EN EL MODO DE MENÚ REFIÉRASE A LAS PÁGINAS 4 Y 5 SW1 Enfriamiento Cool Calefacción Heat El interruptor SW1 debe ajustarse para el modo de funcionamiento del sistema como muestra la figura Para evita...

Страница 16: ...ras carnes en super mercados exhibidores refrigerados en tiendas de conveniencia calentadores de comida control de calefactor y ciertas aplica ciones industriales ADVERTENCIA Lea y siga con atención todas las instrucciones antes de instalar o utilizar este control para evitar lesiones personales y o daños materiales Para evitar descargas eléctricas lesiones personales y o daños al equipo desconect...

Отзывы: