Sondas de temperatura:

NTC

El control incluye un sensor NTC (coeficiente de temperatura 

negativo), con un cable de 7½ pies de longitud. La longitud 

del cable puede extenderse hasta 400 pies empalmando y 

agregando cable adicional (22 AWG o un diámetro mayor) 

PTC

El control podrá conectarse a un sensor PTC (coeficiente de 

temperatura positivo) existente. Asegúrese de que el sensor 

PTC cumpla con las especificaciones de las tablas incluidas 

a continuación. De lo contrario, podrían producirse impreci-

siones de temperatura. La entrada PTC no podrá extenderse 

 

Temperatura

 

Resistencia

 

(°F) 

(°C) 

(K

)

 

-40 

-40 

328.29

 

-31 

-35 

236.83

 

-22 

-30 

172.90

 

-13 

-25 

127.65

 

-4 

-20 

95.23

 

-15 

71.74

 

14 

-10 

54.56

 

23 

-5 

41.85

 

32 

32.37

 

41 

25.23

 

Temperatura

 

Resistencia

 

(°F) 

(°C) 

(K

)

 

50 

10 

19.82

 

59 

15 

15.67

 

68 

20 

12.48

 

77 

25 

10.00

 

86 

30 

8.07

 

95 

35 

6.55

 

104 

40 

5.34

 

113

 

45 

4.38

 

122 

50 

3.61

 

131 

55 

2.99

 

Temperatura

 

Resistencia

 

(°F) 

(°C) 

(K

)

 

140 

60 

2.49

 

149 

65 

2.09

 

158 

70 

1.76

 

167 

75 

1.48

 

176 

80 

1.26

 

185 

85 

1.07

 

194 

90 

0.92

 

203 

95 

0.79

 

212 

100 

0.68

 

221 

105 

0.59

TABLAS DE TEMPERA

TURA VS. RESISTENCIA

 NTC

 

Temperatura

 

Resistencia

 

(°F) 

(°C) 

(

)

 

-40 

-40 

613

 

-31 

-35 

640

 

-22 

-30 

668

 

-13 

-25 

697

 

-4 

-20 

727

 

-15 

758

 

14 

-10 

789

 

23 

-5 

822

 

32 

855

 

41 

889

 

Temperatura

 

Resistencia

 

(°F) 

(°C) 

(

)

 

50 

10 

924

 

59 

15 

960

 

68 

20 

997

 

77 

25 

1035

 

86 

30 

1074

 

95 

35 

1113

 

104 

40 

1153

 

113

 

45 

1194

 

122 

50 

1236

 

131 

55 

1279

 

Temperatura

 

Resistencia

 

(°F) 

(°C) 

(

)

 

140 

60 

1323

 

149 

65 

1368

 

158 

70 

1413

 

167 

75 

1459

 

176 

80 

1506

 

185 

85 

1554

 

194 

90 

1602

 

203 

95 

1652

 

212 

100 

1702

 

221 

105 

1753

TABLAS DE TEMPERA

TURA VS. RESISTENCIA

 PTC

según sea necesario. La polaridad no es importante. Si ex-

tiende la longitud del cable, verifique que la temperatura sea 

precisa y utilice los ajustes de compensación de temperatura 

ambiente (OFS) del menú para compensarla en caso de que 

sea necesario.

más de 50 pies y el cable deberá tener un calibre de 18 

AWG o un diámetro más grande. 

Asegúrese de que la sonda 

conectada sea compatible con las especificaciones de las 

tablas de resistencia vs. temperatura, ya que de lo contrario 

podrían producirse imprecisiones de temperatura.

ESPECIFICACIONES

Relé de salida de carga:   

Valores nominales

 

 

 

 

 

  

 

eléctricos (máximos):

 

120VCA 208VCA

 240VCA

Carga total A NC y carga

 

16 A 

9.2 A 

8 A

Rotor bloqueado A NC y carga

 

96 A 

55.2 A 

48 A

No inductivo A NC y carga

 

16 A 

16 A 

16 A

Caballos de fuerza NC y carga 

1 hp 

1 hp 

1 hp

24 VCA NC y carga 

 

100 VA, 30 VCA

 máx. (clase 2)

Piloto NC y carga  

125 VA, 24 a 240 VCA

 

Carga mínima nominal: 1 

A a 24 VCA

  

 

 

Nota: la corriente/voltaje mínimos anteriores están

 

 

especificados para asegurar un funcionamiento 

 

 

adecuado.

NOTA: 

para uso en circuitos de una sola fase únicamente.

Valores nominales eléctricos del Relé de alarma

 

(máximos):

Contacto N/O: 1 A, 5 a 24 V

, CA o CC

Valores ambientales operativos nominales (Caja de 

control):

Temperatura operativa: 

  

         

-29°F a 140°F (-34° a 60°C)

Valores ambientales de almacenamiento y transporte 

 

nominales:

Temperatura de almacenamiento:  -

40°F a 185°F (-40° a 85°C)

Humedad operativa: 

             

0 a 95% humedad relativa, 

 

             

sin condensación

Punto de rocío máximo:   

            85°F (29°C)

Rango de temperaturas de referencia:

Rango de referencia: 

           

 -40° a 220°F (-40° a 104°C)

Rango diferencial: 

          1 a 30 (°F o °C)

Caja:

Caja NEMA 1, calificación de inflamabilidad: UL94VO

Содержание 16E09-101

Страница 1: ...applications which range from refrigeration to heating due to the wide temperature range of the control stated above Typical applications include walk in freezers beverage coolers supermarket display cases for flowers produce meats convenience store refrigerated cases food warmers boiler control and certain industrial applications Save these instructions for future use WARNING 16E09 101 Optional A...

Страница 2: ...E REFER TO PAGE 6 STATUS INDICATOR LED LIT WHEN CONTROLLED LOAD IS ENERGIZED ON SEE NOTE TEMPERATURE UP BUTTON TEMPERATURE DOWN BUTTON MENU BUTTON PRESS TO ENTER MENU MODE REFER TO PAGES 4 5 SW1 Refrigeration Cool Heating Heat Switch SW1 must be set for system mode as shown To prevent electrical shock and or equipment dam age disconnect electric power to system at main fuse or circuit breaker box ...

Страница 3: ... optional connection to customer alarm equipment Binary Input Gold Plated Contacts 24 VAC Block not used TH Thermostat Hot TR Thermostat Return NTC Temperature Sensor PTC Temperature Sensor Fig 3 Line Voltage Application Power Stealing 120 VAC Hot Neutral L1 L2 208 240 VAC Voltage Input Load Power Stealing Power Stealing is an electronic design within the control that can eliminate the need to con...

Страница 4: ...s how the set point temperature will operate the load terminal CI indicates the setpoint temperature will be the Cut In temperature CO indicates the temperature will be the Cut Out temperature See Operation section SOF Sensor Operation Failure Cool Heat 1 0 0 or 1 None Cooling Selects the operation of the Control Load relay in the event of a sensor failure in Cool mode 1 default will cause the loa...

Страница 5: ...l Set Point SP Cut In Differential 5 Setpoint temperature 40 Temperature Range 40 Setpoint Cut Out 45 SW1 Cool Set Point SP Cut Out Differential 5 Setpoint temperature 40 Temperature Range HEAT To use as a Heating control SW1 must be set to Heat The flame icon will display If control is in Heat mode and Set Point is selected as the Cut Out Temperature Operating Setpoint Differential Range Temperat...

Страница 6: ... should be given to these events to prevent a false alarm If the control set back feature is used to change the setpoint the delay period set in AL should consider the time it takes for the system to reach the set back temperature to avoid a false alarm Power Loss If the temperature control experiences an input power failure the control will close the alarm relay before total power of the control ...

Страница 7: ...Resistance KΩ 140 60 2 49 149 65 2 09 158 70 1 76 167 75 1 48 176 80 1 26 185 85 1 07 194 90 0 92 203 95 0 79 212 100 0 68 221 105 0 59 Temperature F C Resistance KΩ 40 40 613 31 35 640 22 30 668 13 25 697 4 20 727 5 15 758 14 10 789 23 5 822 32 0 855 41 5 889 Temperature F C Resistance KΩ 50 10 924 59 15 960 68 20 997 77 25 1035 86 30 1074 95 35 1113 104 40 1153 113 45 1194 122 50 1236 131 55 127...

Страница 8: ... line 1 888 725 9797 www white rodgers com www emerson com White Rodgers is a division of Emerson Electric Co The Emerson logo is a trademark and service mark of Emerson Electric Co TROUBLESHOOTING Temperature differential is wider than set Temperature change of customer s unit is fast and the Anti Short Cycle delay setting may be overriding the call to activate the heat or cool Solution lower Ant...

Страница 9: ... descongelación o cualquier otro dispositivo con la función de alarma activada Esto produciría una falsa alarma Si la función de alarma está activada conecte según el diagrama de Non Power Stealing El diferencial de temperatura es más amplio que el ajustado El cambio de temperatura de la unidad del cliente es rápido y el ajuste de demora anti ciclo corto podría estar anulando la llamada para activ...

Страница 10: ... DE TEMPERATURA VS RESISTENCIA PTC según sea necesario La polaridad no es importante Si ex tiende la longitud del cable verifique que la temperatura sea precisa y utilice los ajustes de compensación de temperatura ambiente OFS del menú para compensarla en caso de que sea necesario más de 50 pies y el cable deberá tener un calibre de 18 AWG o un diámetro más grande Asegúrese de que la sonda conecta...

Страница 11: ...rio cambie la opción de menú LP a On Al salir del menú cuando se guarden los ajustes las teclas o y quedarán desactivadas del uso normal Para desbloquear el teclado presione y manténgalo presionado durante 5 segundos La pantalla cambiará y mostrará LP On Presione o por un momento para cambiar el ajuste a Off y luego presione durante algunos instantes El control volverá a su funcionamiento normal y...

Страница 12: ...la temperatura de referencia se selecciona como temperatura de desconexión Rango operativo de Temperatura Diferencial temperatura de referencia más Ejemplo 40 Temperatura de referencia Temperatura de desconexión 45 SW1 Enfriamiento Temperatura de referencia SP Temperatura de desconexión Diferencial 5 Temperatura de referencia 40 Rango de temperatura CALOR HEAT Para usar como control de calefacción...

Страница 13: ...ado Off On u Off del panel frontal OFS Compensación de 0 4 3 2 1 0 temperatura ambiente 1 2 3 4 Opción Ajuste Opciones del de Presione o menú Descripción fábrica para seleccionar Observaciones Enfriamiento Selecciona el funcionamiento del relé de carga de control en caso de una falla del sensor en el modo Frío 1 ajuste predeterminado hace que los contactos de carga del relé se cierren y si el sens...

Страница 14: ...e alarma Para la conexión opcional al equipo de alarma del cliente NTC Coeficiente de temperatura negativo PTC Coeficiente de temperatura positivo NOTA Sólo es posible conectar un sensor PTC o NTC El sensor debe cumplir con las especificaciones de temperatura vs resistencia indicadas Power Stealing Power Stealing es una característica electrónica del control que elimina la necesidad de conectar un...

Страница 15: ...6 LED INDICADOR DE ESTADO SE ENCIENDE CUANDO LA CARGA CONTROLADA ESTÁ ENERGIZADA ON VEA LA NOTA BOTÓN DE INCREMENTO DE TEMPERATURA BOTÓN DE REDUCCIÓN DE TEMPERATURA BOTÓN DE MENÚ PRESIONE PARA INGRESAR EN EL MODO DE MENÚ REFIÉRASE A LAS PÁGINAS 4 Y 5 SW1 Enfriamiento Cool Calefacción Heat El interruptor SW1 debe ajustarse para el modo de funcionamiento del sistema como muestra la figura Para evita...

Страница 16: ...ras carnes en super mercados exhibidores refrigerados en tiendas de conveniencia calentadores de comida control de calefactor y ciertas aplica ciones industriales ADVERTENCIA Lea y siga con atención todas las instrucciones antes de instalar o utilizar este control para evitar lesiones personales y o daños materiales Para evitar descargas eléctricas lesiones personales y o daños al equipo desconect...

Отзывы: