Server power and cooling information
contains specifications for the server power consumption and
dissipation. Calculations based on this table are intended to provide maximum power
and heat dissipation. EMC provides a power and weight calculator at
. Use this calculator to refine the power and heat values in the
table below to more-closely match the specific server hardware configuration. Ensure that
the server installation site meets the requirements for your configuration.
Table 1 Server power consumption and dissipation
Requirement
Description
-
-
AC line voltage
90-264 V AC, autoranging, 47- 63 Hz
Power consumption
(operating maximum)
420 VA (412 W) maximum (fully configured)
Heat dissipation
14.832 x 10
5
J/hr (1406 BTU/hr) maximum
Maximum inrush current
55 A per power supply for 6 ms or less under typical line
conditions and over the entire system ambient operating range
Server dimensions and weight
Table 2 Server dimensions and weight
Dimension
Server
Server with rails
-
-
-
Height
1.68 in (4.26 cm)
1.0 U (with or without bezel)
Depth
21.8 in (55.37 cm)
24 in to 29.5 in (61 cm to 74.9 cm)
Width
17.4 in (44.31 cm) without
cabinet latch brackets
18.99 in (48.24 cm) with cabinet latch
brackets
Maximum weight
23.3 lb (10.57 kg)
28.3 lb (12.84 kg)
Server placement requirements
There are no restrictions on the location of the server in the cabinet. Allow at least 36
inches of service clearance in front of the cabinet. Power distribution must support the
number of outlets required for the server and the server power rating listed on the Device
2
EMC SVR-I1U-1304 Server Installation and Maintenance Guide