![EMC FC4400 Скачать руководство пользователя страница 121](http://html1.mh-extra.com/html/emc/fc4400/fc4400_hardware-reference-manual_2399719121.webp)
A
Operating Limits
A-7
Specifications and Operational Requirements
Operating Limits
The ambient temperature specification is measured at the front door
inlet. The site must have air conditioning of the correct size and
placement to maintain the specified ambient temperature range. The
air conditioning must be able to handle the BTU requirements of the
DPE and DAEs.
The operating limits for temperature and humidity must not be exceeded
inside the deskside DPE.
Requirement
Description
Ambient temperature
10
o
C to 40
o
C (50
o
F to 104
o
F)
Temperature gradient
10
o
C/hr (50
o
F/hr)
Relative humidity
20% to 80% noncondensing
Elevation
2438 m (8,000 ft) at 40
o
C, 3077 m (10,000 ft) at 37
o
C
Drive module power
25 W drive slot maximum (seeking)
Содержание FC4400
Страница 6: ...EMC Disk Array Processor Enclosure DPE Deskside Model FC4400 4500 Hardware Reference vi Contents ...
Страница 10: ...x EMC Disk Array Processor Enclosure DPE Deskside Model FC4400 4500 Hardware Reference Figures ...
Страница 12: ...xii EMC Disk Array Processor Enclosure DPE Deskside Model FC4400 4500 Hardware Reference Tables ...
Страница 16: ...xvi EMC Disk Array Processor Enclosure DPE Deskside Model FC4400 4500 Hardware Reference Preface ...
Страница 128: ...g 6 EMC Disk Array Processor Enclosure DPE Deskside Model FC4400 4500 Hardware Reference Glossary ...
Страница 134: ...EMC Disk Array Processor Enclosure DPE Deskside Model FC4400 4500 Hardware Reference i 6 Index ...