MAINTENANCE 

 
Due to the Reverse Polarity system that avoids scale in the plates of the cell, the first action to consider for 
ensuring a long cell lifetime is to keep the chemical parameters always in the recommended range, especially 
the amount of salt, the pH and the water hardness. 
 
1.

 

Keep the salinity of the water always higher than 3000 ppm in order to avoid premature deterioration 

of the cell plates. The following formula determines the amount of salt to be added in the pool due to low 
salinity: 

Q = (4-S) x V 

Where  Q = quantity of salt (kg) to be added. 

4 = correct salt concentration (constant). 
S = Measured salt content in the pool 
V = Volume of the pool in m3. 

2.

 

Keep the pH between 7.2 and 7.6. Check and clean the cell plates if the system has been working for 

a prolonged period with a pH value over 7.6. 

 

ELECTROLYTIC CELL CLEANING PROCEDURE 

If scale has formed on the titanium plates, the first cleaning procedure is as follows: 

1 .

 

Switch off the power supply of 

SSCmini

®

 

control unit and remove electrodes from the cell. 

2 .

 

Once removed, look inside and inspect for scale formation on the plates and for any debris which 

has passed through the filter and caught on the plates. 

3.

 

Try to remove the scale using a plastic or wooden tool (do NOT use metal as this will scratch the 

coating off the plates). 

If the scale still remains on the plates, proceed the cell cleaning with acid solution: 

1.

 

Dilute hydrochloric acid with water: one part of acid in 10 parts of water.   
ATTENTION! Always add acid into the water, NEVER add water into the acid. This prevents splashing 
of the acid when the water hits it. Wear rubber gloves and appropriate eye protection. 

2.

 

Submerge the cell plates in the solution for no more than 10 minutes. Plates plastic housing can be 
submerged in the solution, but avoid any contact with the cell connections and wires. 

3.

 

Rinse the cell with a high pressure hose. If any deposits are still visible, repeat soaking and rinsing. 

4.

 

If scaling persists, replace the cell by a new one. 

 
 

11.

 

WINTERIZING 

 
During a long non-working period, such as winter, the following procedure must be carried out: 

 

Switch off 

SSCmini

®

 

control unit and disconnect it from power supply. 

 

Drain all water from the electrolytic cell, as well as filtration pump, filter and piping. 

 

Clean the cell plates with fresh water and dry them with a soft cloth. Check if scaling has been 
formed. If so, proceed with cleaning of the cell plates (see chapter 10).

 

 

Содержание SSC mini

Страница 1: ...1 SALT CHLORINATOR USER MANUAL SSCmini...

Страница 2: ...side the wiring compartment To reduce the risk of electric shock this terminal must be connected to the grounding means provided in the electric supply service panel with a continuous copper wire equi...

Страница 3: ...acteria the above reactions will continuously recycle virtually eliminating the need to add sanitizing chemicals to your pool The only time you may need to add more salt to the pool is when water is r...

Страница 4: ...lkalinity 80 120 ppm Calcium Hardness 200 400 ppm Metal 0 ppm 6 1 SALT LEVEL The amount of salt required when using Emaux SSCmini is between 4000 and 6000 ppm To reach this concentration it is necessa...

Страница 5: ...enclosure that is suitable for outdoor mounting IPX4 rating However the following points must be taken into consideration for a correct installation of the control unit 1 Install the Control Unit usi...

Страница 6: ...ed in a vertical position 8 START UP Before starting up Emaux SSCmini unit the following points have to be taken into consideration 1 Check if the filter is completely clean and ensure that the swimmi...

Страница 7: ...ng guide Chapter 12 3 Alarm The unit is not working properly Refer to the Troubleshooting guide Chapter 12 4 Stand by The unit is in between operation cycles 5 Normal operation Electrolytic cell is ge...

Страница 8: ...LED is ON A new cycle will start at 10 00 until 10 30 and so on If you activate Superchlorination mode at 10 30 Superchlorination LED is ON then the unit will be working until 10 30 of the next day a...

Страница 9: ...ebris which has passed through the filter and caught on the plates 3 Try to remove the scale using a plastic or wooden tool do NOT use metal as this will scratch the coating off the plates If the scal...

Страница 10: ...pply Disconnect the unit from power supply for two minutes and then connect it again Ensure that SSCmini is receiving 220V 240VAC 50 60H input LED 4 Water temperature out of working range Test water t...

Страница 11: ...equipment or installation type 4 Damage due to unauthorized product modifications or failure to use Emaux original replacement parts 5 Damage caused by negligence or failure to properly maintain produ...

Страница 12: ...chnical operations Emaux is not liable for any loss of time inconvenience incidental expenses such as labor cost phone calls legal cost or material cost incurred in connection with the replacement or...

Отзывы: