description
Defines whether the ems controller displays the temperature
3.0
, or the word
US E
during the ready
mode.
ems controllers always display alarms.
considerations None
range
00 (
US E
) or 01 (temperature)
global default
01 (temperature)
10.19
delay to saving (dS)
The table below details the delay to saving (
dS
) parameter.
display
description
Defines the delay in switching to the
saving mode
from
ready mode
.
The delay starts at the end of the last active 30 minute
period of the
ready mode
.
considerations Must be set in multiples of 30 minutes.
range
0 to 120 minutes (in multiples of 30 minutes)
global default
00 (no delay)
10.20
defrost termination temperature (dtd)
The table below details the defrost temperature duration (
dtd
) parameter.
display
description
Defines the temperature to end the defrost cycle.
Ending defrost cycles on temperature minimizes the duration of defrost cycles.
The temperature is measured as follows:
l
OFC
and sub-zero coolers: the temperature is measured on the evaporator sensor.
l
GDC
coolers: the temperature is measured on the appliance sensor.
considerations
l
Must be set above the set point (
S P
) plus differential (
dI F
) temperature.
l
Must be set below
I Pd
.
l
If icing up occurs, review the values of the defrost parameters.
range
1 to 30ºC (33 to 86ºF)
ems75sz: -5 to 22ºC (23 to 71ºF)
global default
9.0ºC (48ºF)
ems75sz: 15.0ºC (59ºF)
10.21
defrost termination method (dtF)
The table below details the defrost termination method (
dtF
) parameter.
ems55advanced and ems55Radvanced / General Use
73 of 84