10.2
parameter by owners
The parameter owners are usually defined as performance, design, and operational parameters with different organizations
being responsible for each set.
performance
(brand)
set point (
S P
) and differential (
dI F
)
saving set point (
S S P
) and saving differential (
S d
)
saving restart (
S r
)
design
(OEMs)
defrost method (
dF
) and defrost termination method
(
dtF
)
defrost interval (
dE
) and defrost duration (
dd
)
defrost activation temperature (
ddt
) and defrost termination temperature (
dtd
)
defrost heater (
dHr
)
compressor rest time (
rt
)
fan cycle on (
FC O
) and fan cycle off (
FC F
)
calibration 1 (
C A1
) and calibration 2 (
C A2
)
operation
(operators)
Celsius or Fahrenheit (
C F
)
saving temperature disable (
PEr
)
freeze-up protection (
dtt
)
delay to saving mode (
dS
)
learning period (
L P
) and activity frequency (
AF
)
display (
dI S
) and display stability (
d2
)
light delay (
L d
) and marketing mode (
Ar
)
fan set point (
FS P
)
alarm delay (
Ad
), buzzer enable (
b0
) and buzzer duration (
b1
)
refrigeration system failure (
C t
)
condenser high temperature (
Ht
)
10.3
alarm delay (Ad)
The table below details the alarm delay (
Ad
) parameter.
display
description
Defines the maximum time the cooler door can be open before sounding the alarm buzzer.
considerations
If disabled, the door switch is also disabled.
The ems controller does not detect door openings, therefore, the ems controller does not:
l
update the self-learning matrix for door activity.
l
manage the evaporator fan management for door activity.
l
sound door alarms if the door is left open.
range
00 to 30 minutes
global default
00 (disabled)
10.4
activity frequency (AF)
The table below details the activity frequency (
AF
) parameter.
ems55advanced and ems55Radvanced / General Use
67 of 84