6.17. CO2 PI-control
If you activate air quality control, you can use the following settings to define control
type, setpoint values, and ventilation.
General control
The
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D
can be used to control one
or two-stage ventilation.
Configure a block for the ventilation control using the blocking object.
Specify when the current control variables are to be sent to the bus. Periodic sending
is safer, in case a message does not reach a recipient. You may also set up periodic
monitoring using an actuator with this setting.
The status object shows the current status of the output variable (0 = OFF, >0 = ON) and
can for example be used for visualisation.
Switching output sends on change to 1
• Do not send message
• if switching output = 1
send 1
Switching output sends on change to 0
• Do not send message
• if switching output = 0
send 0
Switching output sends on change and
periodically
Send switching output status
Switching output sends on change to 1
and periodically
if switching output = 1
send 1
Switching output sends on change to 0
and periodically
if switching output = 0
send 0
Use control
Yes
• No
Type of control
• One-stage ventilation
• Two-stage ventilation
Behaviour of the blocking object with value
• 1 = Block | 0 = release
• 0 = block | 1 = release
Blocking object value
before first communication
0 • 1
Send control variable
• on change
• on change and periodically
at and above change of (in ppm)
1...20; 2
Cycle
(
if sent periodically)
5 s • ... • 5 min • … • 2 h