6.12. Comfort field
The
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D
can send a message to the
bus if the limits of the comfort field are exceeded. In this way, it is for example possible
to monitor compliance with DIN 1946 (standard values) or even to define your own
comfort field.
Specify the
sending pattern
, a
Text
for comfortable and uncomfortable and the
Ob-
ject value
.
Define the comfort field by specifying the minimum and maximum values for tempe-
rature and humidity. The specified standard values comply with DIN 1946
Use absolute humidity
No • Yes
Sending pattern
• never
• periodically
• on change
• on change and periodically
At and above change of
(if sent on change)
0.1 g • 0.2 g • 0.5 g • 1.0 g • 2.0 g • 5.0 g
Send cycle
(if sent periodically)
5 s • 10 s • 30 s… • 2 h
Use comfort field
No • Yes
Sending pattern
• never
• periodically
• on change
• on change and periodically
Text for comfortable
[Free text max. 14 chars.]
Text for uncomfortable
[Free text max. 14 chars.]
Object value is at
• comfortable = 1 | uncomfortable = 0
• comfortable = 0 | uncomfortable = 1
Send cycle
(if sent periodically)
5 s • 10 s • 30 s… • 2 h
Maximum temperature in °C
(Standard 26°C)
25 ... 40; 26
Minimum temperature in °C
(Standard 20°C)
10 ... 21; 20
Maximum relative humidity in %
(
Standard 65%)
52 ... 90; 65
Minimum relative humidity in %
(Standard 30%)
10 ... 43; 30
Maximum absolute humidity in 0.1 g/kg
(Standard 115 g/kg)
50 ... 200; 115