Parameter setting
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D
• Version: 10.09.2018 • Technical changes and errors excepted.
The
increment
for the setpoint changes is predefined. Whether the change only re-
mains temporarily active (not saved) or is also retained after power supply restoration
(and programming), is specified in the first section of "General control". This also ap-
plies to a comfort extension.
The control may be reset to comfort mode from eco mode, which is used as night mo-
de, via the comfort extension. This allows the user to maintain the comfort setpoint
value for a longer time, e.g. when having guests. The duration of this comfort extensi-
on period is set. After the comfort extension period expires, the system returns to eco
mode.
Comfort Setpoint
Comfort mode is usually used for daytime mode when people are present. A starting
value is defined for the comfort setpoint as well as a temperature range in which the
setpoint value may be modified.
If setpoint values are entered separately:
If the comfort setpoint value is used as a basis:
If the comfort setpoint value is used as a basis, the reduction/increment of the value is
set.
If the comfort setpoint is used as the basis without a switching object, a dead zone is
specified for the control mode "heating
and
cooling" to avoid direct switching from he-
ating to cooling.
Increment for setpoint changes
(in 0.1 °C)
1… 50; 10
Comfort extension time in seconds
(can only be activated from eco mode)
1…36000; 3600
Starting heating/cooling setpoint (in 0.1 °C)
valid until 1st communication
(not upon saving the setpoint value after
programming)
-300…800; 210
Min. object value heating/cooling
(in 0.1 °C)
-300…800; 160
Max. object value heating/cooling
(in 0.1 °C)
-300…800; 280
Minimum base setpoint (in 0.1°C)
-300…800; 160
Maximum base setpoint (in 0.1°C)
-300…800; 280
Reduction by up to (in 0.1°C)
0…200; 50
Increase by up to (in 0.1°C)
0…200; 50
Dead zone between heating and cooling
(only if both heating AND cooling are used)
1…100; 50