53
Parameter setting
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D
• Version: 10.09.2018 • Technical changes and errors excepted.
Temperature hysteresis: 1°C
Relative humidity hysteresis: 2% RH
Absolute humidity hysteresis: 2 g/kg
The following air pressure settings are only available for the
Sewi KNX AQS/TH-D model.
6.13. Air Pressure Measurement
If necessary, activate the air pressure malfunction object. Specify at which
height
abo-
ve sea level the device is installed and whether the reading is to be additionally output
as
barometric pressure
(see below
information on air pressure
).
Define the
transmission pattern
and, if necessary, activate the
minimum and ma-
ximum value
(these values are not retained after a reset).
Dependent on the air pressure measured, a
Text object
can be sent. Specify the sen-
ding pattern and enter the text.
Use malfunction object
No • Yes
Height above sea level
-1000...10000; 200
Additionally output measured value
as barometric pressure
No • Yes
Sending pattern for measured value
• never
• periodically
• on change
• on change and periodically
at and above change of
(if sent on change)
10 Pa • 20 Pa • 50 Pa • 100 Pa • 200 Pa •
500 Pa
Send cycle
(if sent periodically)
5 s ... 2 h; 1 min
Use minimum and maximum value
No • Yes
Sending pattern for text object
• never
• periodically
• on change
• on change and periodically
Text for normal pressure range
< 98,000 Pa
(e.g. weather is stormy)
stormy
98,000...100,000 Pa
(e.g. weather is rainy)
rainy
100,000...102,000 Pa
(e.g. weather is changeable)
changeable