17
Transfer protocol
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D
• Version: 10.09.2018 • Technical changes and errors excepted.
405
Air pressure sensor: Min. normal
measurement [Pa]
Output
R-CT
[14.58] DPT_Val-
ue_Pressure
4 bytes
406
Air pressure sensor: Min. barometric
measurement [Pa]
Output
R-CT
[14.58] DPT_Val-
ue_Pressure
4 bytes
407
Air pressure sensor: Max. normal
measurement [Pa]
Output
R-CT
[14.58] DPT_Val-
ue_Pressure
4 bytes
408
Air pressure sensor: Max. barometric
measurement [Pa]
Output
R-CT
[14.58] DPT_Val-
ue_Pressure
4 bytes
409
Air pressure sensor: Min./Max.
measurement reset
Input
-WC-
[1.017] DPT_Trig-
ger
1 bit
410
Air pressure sensor: Pressure range
text
Output
R-CT
[16.0]
DPT_String_ASCII
14
bytes
411
Air pressure threshold value 1:
Absolute value
Input/
Output
RWCT [14.58] DPT_Val-
ue_Pressure
4 bytes
412
Air pressure threshold value 1:
(1:+ | 0:-)
Input
-WC-
[1.1] DPT_Switch
1 bit
413
Air pressure threshold value 1:
Delay from 0 to 1
Input
-WC-
[7.5] DPT_Time-
PeriodSec
2 bytes
414
Air pressure threshold value 1:
Delay from 1 to 0
Input
-WC-
[7.5] DPT_Time-
PeriodSec
2 bytes
415
Air pressure threshold value 1:
Switching output
Output
R-CT
[1.1] DPT_Switch
1 bit
416
Air pressure threshold value 1:
Switching output block
Input
-WC-
[1.1] DPT_Switch
1 bit
417
Air pressure threshold value 2:
Absolute value
Input/
Output
RWCT [14.58] DPT_Val-
ue_Pressure
4 bytes
418
Air pressure threshold value 2:
(1:+ | 0:-)
Input
-WC-
[1.1] DPT_Switch
1 bit
419
Air pressure threshold value 2:
Delay from 0 to 1
Input
-WC-
[7.5] DPT_Time-
PeriodSec
2 bytes
420
Air pressure threshold value 2:
Delay from 1 to 0
Input
-WC-
[7.5] DPT_Time-
PeriodSec
2 bytes
421
Air pressure threshold value 2:
Switching output
Output
R-CT
[1.1] DPT_Switch
1 bit
422
Air pressure threshold value 2:
Switching output block
Input
-WC-
[1.1] DPT_Switch
1 bit
423
Air pressure threshold value 3:
Absolute value
Input/
Output
RWCT [14.58] DPT_Val-
ue_Pressure
4 bytes
424
Air pressure threshold value 3:
(1:+ | 0:-)
Input
-WC-
[1.1] DPT_Switch
1 bit
425
Air pressure threshold value 3:
Delay from 0 to 1
Input
-WC-
[7.5] DPT_Time-
PeriodSec
2 bytes
No.
Text
Func-
tion
Flags
DPT Typ
Size