63
Parameter setting
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D
• Version: 10.09.2018 • Technical changes and errors excepted.
6.19. Computer
Activate the multi-functional computer, with which the input data can be changed by
calculation, querying a condition or converting the data point type. The menus for the
further setting of the computer are then displayed.
6.19.1. Computer 1-8
Set, in which cases input values received are to be kept per object. Please note that the
setting "After power restoration and programming" should not be used for the initial
start-up, as the factory settings are always used until the first call (setting via objects is
ignored).
Output delivers
• Maximum value
• Minimum value
• Average value
Use input 1 / 2 / 3 / 4 / 5
No • Yes
Output sends
• on change of output
• on change of output and periodically
• when receiving an input object
• when receiving an input object and
periodically
Send cycle
(if sent periodically)
5 s • 10 s • 30 s • ... • 5 min • … • 2 h
At and above change of
(if sent on change)
1% • 2% • 5% • 10% • 20% • 25% • 50%
Analysis of the blocking object
• at value 1: block | at value 0: release
• at value 0: block | at value 1: release
Blocking object value
before 1st communication
0 • 1
Behaviour of the switching output
On block
• do not send message
• Send value
Sent value in %
0 ... 100
output sends on release
(with 2 seconds release delay)
• the current value
• the current value after receipt of an object
Computer 1/2/3/4/5/6/7/8
No • Yes
Maintain the
input values received via communication
objects
• never
• after power supply restoration
• after power supply restoration and
programming