18
Setting of parameters
Wind Sensor KNX W
• Date of issue: 31.10.2012 • Technical changes reserved. Errors reserved.
Blocking
„Blocking“ only appears if using „Switching output sends on change“
If block of the switching output is used:
6.3.
Logic
AND Logic
OR Logic
Switching delay from 0 to 1
none • 1 sec … 2 h
Switching delay from 1 to 0
none • 1 sec … 2 h
Switching output sends
• not
• on change
• on change to 1
• on change to 0
• on change and periodically
• on change to 1 and periodically
• on change to 0 and periodically
send periodically all
(only if sending “periodically“)
5 sec … 2 h
Use block of the switching output
Yes • No
Use block of the switching output
Yes
Evaluation of the blocking object
• if value 1: block | if value 0: release
• if value 0: block | if value 1: release
Value of the blocking object before
1. communication
0 • 1
Behaviour of the switching output
with blocking
• do not send telegram
• send 0
• send 1
Behaviour of the switching output
with release (selection depends on settings
made before)
• do not send telegram
• send status of the switching output
• if switching output = 1 => send 1
• if switching output = 0 => send 0
Communication objects logic inputs
do not release • release
Logic 1 / 2 / 3 / 4 / 5 / 6 / 7 / 8
not active • active
Transmission delay of the switching
outputs after power up and programming
5 sec … 2 h
Logic 1 / 2 / 3 / 4 / 5 / 6 / 7 / 8
not active • active
Transmission delay of the switching
outputs after power up and programming
5 sec … 2 h