22
Parameter setting
Brightness and Wind Sensor KNX LW sl
• Status: 19.08.2021 • Errors excepted. Subject to technical changes.
6.1.
General settings
Set basic characteristics of data transfer. A different transmission delay prevents an
overload of the bus shortly after the reset.
6.2.
Brightness measurement value
Set the send pattern for the measured brightness.
6.3.
Brightness threshold values
Activate the brightness threshold values required (maximum four) The menus for the
further setting of the threshold values are then displayed.
6.3.1. Brightness threshold value 1-4
Threshold value
Set, in which cases threshold values and delay times received are to be kept per object.
The parameter is only taken into consideration if the specification/ setting by object is
activated further down. Please note that the setting "After power restoration and pro-
Transmission delay after reset/restoration of bus for:
Measured values
5 … 300 seconds
Threshold values and switching outputs
5 … 300 seconds
Computer objects
5 … 300 seconds
Logic objects
5 … 300 seconds
Maximum telegram quota
1 • 2 • 5 • 10 • 20 • 50 Telegrams per sec.
Send pattern
• never
• periodically
• on change
• on change and periodically
at and above change in %
(if sent on change)
1 ... 100; 20
Send cycle
(if sent periodically)
5 s ... 2 h
Threshold value 1
No • Yes
Threshold value...
No • Yes
Threshold value 4
No • Yes
Содержание KNX LW sl 70164
Страница 1: ...Item number 70164 EN KNX LW sl Brightness and Wind Sensor Installation and Adjustment ...
Страница 2: ......