35
Parameter setting
Brightness and Wind Sensor KNX LW sl
• Status: 19.08.2021 • Errors excepted. Subject to technical changes.
6.9.
Logic
The device has 16 logic inputs, eight AND and eight OR logic gates.
Activate the logic inputs and assign object values up to first call.
Activate the required logic outputs.
AND logic
OR logic
6.9.1. AND logic 1-8 and OR logic outputs 1-8
The same setting options are available for AND and OR logic.
Each logic output may transmit one 1 bit or two 8 bit objects. Determine what the out
put should send if logic = 1 and = 0.
Value before first call
0 • 1
Output pattern
On block
• do not send anything
• send value
On release
• as send pattern [see above]
• send current value immediately
Use logic inputs
Yes • No
Object value prior to first call for:
- Logic input 1
0 • 1
- Logic input ...
0 • 1
- Logic input 16
0 • 1
AND logic 1
not active • active
AND logic ...
not active • active
AND logic 8
not active • active
OR logic 1
not active • active
OR logic ...
not active • active
OR logic 8
not active • active
1. / 2. / 3. / 4. Input
• do not use
- Logic inputs 1...16
- Logic inputs 1...16 inverted
• all switching events that the device
provides (see
Connection inputs of the
AND/OR logic
)
Output type
• a 1-Bit-object
• two 8-bit objects