Parameter setting
6.0.1. Behaviour on power failure/power restoration
Behaviour on bus or auxiliary power failure
The device sends nothing.
Behaviour on bus or auxiliary voltage restoration and following programming
or reset
The device sends all measurement values as well as switching and status outputs ac-
cording to their send pattern set in the parameters with the delays established in the
"General settings" parameter block. The "Software version" communications object is
sent once after 5 seconds.
6.0.2. Storage of threshold values
For threshold values that are specified via a communication object, a starting value
must be entered for the first commissioning. It is valid until the first communication of
a new threshold value.
After this, a threshold value once set per parameter or via a communication object is
retained until a new threshold value is sent via a communication object. The last thres-
hold value set by communication object is saved in the device, so that it is retained du-
ring a power outage and is available once again when power is restored.
6.0.3. Malfunction objects
Malfunction objects are sent after every reset and, additionally, after changes (i.e. at
the beginning and end of a malfunction).
1464 OR logic 6: 8-bit output A
Output
R-CT
1 byte
1465 OR logic 6: 8-bit output B
Output
R-CT
1 byte
1466 OR logic 6: Block
Input
-WC-
[1.1] DPT_Switch
1 bit
1467 OR logic 7: 1-bit switching output
Output
R-CT
[1.2] DPT_Bool
1 bit
1468 OR logic 7: 8-bit output A
Output
R-CT
1 byte
1469 OR logic 7: 8-bit output B
Output
R-CT
1 byte
1470 OR logic 7: Block
Input
-WC-
[1.1] DPT_Switch
1 bit
1471 OR logic 8: 1-bit switching output
Output
R-CT
[1.2] DPT_Bool
1 bit
1472 OR logic 8: 8-bit output A
Output
R-CT
1 byte
1473 OR logic 8: 8-bit output B
Output
R-CT
1 byte
1474 OR logic 8: Block
Input
-WC-
[1.1] DPT_Switch
1 bit
No.
Text
Function Flags
DPT type
Size
Содержание KNX LW sl 70164