27
Parameter settings
Interface KNX B8-TH
• Version: 24.08.2016 • Technical changes and errors excepted.
If the comfort setpoint is used as the basis without a switching object, a dead zone is
specified for the control mode "heating
and
cooling" to avoid direct switching from
heating to cooling.
Standby setpoint
Standby mode is usually used for daytime mode when people are absent.
If setpoint values are entered separately:
A starting setpoint value is defined as well as a temperature range in which the setpoint
value may be changed.
If the comfort setpoint value is used as a basis:
If the comfort setpoint value is used as a basis, the reduction/increment of the value is
set.
Eco setpoint
Eco mode is usually used for night mode.
If setpoint values are entered separately:
A starting setpoint value is defined as well as a temperature range in which the setpoint
value may be changed.
Dead zone between heating and cooling
(only if both heating AND cooling are used)
1…100; 50
Starting heating/cooling setpoint (in 0.1 °C)
valid until 1st communication
-300…800; 210
Min. object value heating/cooling
(in 0.1 °C)
-300…800; 160
Max. object value heating/cooling
(in 0.1 °C)
-300…800; 280
Reduce heating setpoint (in 0.1°C)
(for heating)
0…200; 30
Increase cooling setpoint (in 0.1°C)
(for cooling)
0…200; 30
Starting heating/cooling setpoint (in 0.1 °C)
valid until 1st communication
-300…800; 210
Min. object value heating/cooling
(in 0.1 °C)
-300…800; 160
Max. object value heating/cooling
(in 0.1 °C)
-300…800; 280