Installation and Adjustment

EN

KNX B8-TH

Interface

Item number 70249

Elsner Elektronik GmbH

 Control and Automation Technology

Sohlengrund 16
75395 Ostelsheim 

Phone +49 (0) 70 33/ 30945-0 

[email protected]

Germany Fax 

+49 (0) 70 33 /30945-20 

www.elsner-elektronik.de

Technical support: +49 (0) 70 33 / 30 945-250

Содержание KNX B8-TH

Страница 1: ...Item number 70249 Elsner Elektronik GmbH Control and AutomationTechnology Sohlengrund 16 75395 Ostelsheim Phone 49 0 7033 30945 0 info elsner elektronik de Germany Fax 49 0 7033 30945 20 www elsner el...

Страница 2: ...5 1 Behaviour on power failure restoration of power 19 5 2 General settings 19 5 3 Temperature readings 20 5 4 Temperature threshold values 20 5 4 1 Threshold values 1 8 21 5 5 Temperature PI controll...

Страница 3: ...eshooting of the device must only be carried out by a competent electrician Safety advice Safety advice for working on electrical connections components etc DANGER indicates an immediately hazardous s...

Страница 4: ...standard frames of switch programmes 1 input for temperature sensor T NTC ST Bus warning with regard to whether the values for temperature and air humidity are within the comfort field DIN 1946 Dewpo...

Страница 5: ...accidental switching on Housing Plastic Colour White Assembly Installation Protection category IP 20 Dimensions approx 38 x 49 x 18 W H D mm Weight approx 20 g interface approx 30 g interface incl co...

Страница 6: ...conclusion of all installation and operational start up tasks and only in the surroundings designated for it Elsner Elektronik is not liable for any changes in norms and standards which may occur aft...

Страница 7: ...y inputs 5 8 3 Connection sensor T UP basic or TH UP basic 4 KNX plug terminal 5 Programming key recessed 6 Programming LED recessed 7 Connection temperature sensor T NTC ST 2 3 4 5 6 7 Ill 2 The devi...

Страница 8: ...ialisation phase lasting a few seconds During this phase no information can be received via the bus 3 Addressing of the device at the bus The device is supplied with the bus address 15 15 250 You can...

Страница 9: ...r Reading Output R CT 9 1 DPT_Val ue_Temp 2 bytes 4 Temp plug in sensor Total reading Output R CT 9 1 DPT_Val ue_Temp 2 bytes 5 Temp plug in sensor Min max reading query Input WC 1 17 DPT_Trigger 1 bi...

Страница 10: ...ut Output RWCT 9 1 DPT_Val ue_Temp 2 bytes 24 Temp threshold value 2 1 0 Input WC 1 1 DPT_Switch 1 bit 25 Temp threshold value 2 Switching delay from 0 to 1 Input WC 7 5 DPT_TimePeri odSec 2 bytes 26...

Страница 11: ...itching output Output R CT 1 1 DPT_Switch 1 bit 46 Temp threshold value 5 Switching output block Input WC 1 1 DPT_Switch 1 bit 47 Temp threshold value 6 Absolute value Input Output RWCT 9 1 DPT_Val ue...

Страница 12: ...mp controller Frost heat protection mode activation Input RWCT 1 1 DPT_Switch 1 bit 68 Temp controller Block 1 Blocking Input WC 1 1 DPT_Switch 1 bit 69 Temp controller Current setpoint Output R CT 9...

Страница 13: ...ariable level 2 Output R CT 5 1 DPT_Scaling 1 byte 88 Temperature controller Control variable for 4 6 way valve Output R CT 5 1 DPT_Scaling 1 byte 89 Temp controller Level 1 heating status 1 ON 0 OFF...

Страница 14: ...midity threshold value 2 Absolute value Input Output RWCT 9 7 DPT_Value_Hu midity 2 bytes 109 Humidity threshold value 2 1 0 Input WC 1 1 DPT_Switch 1 bit 110 Humidity threshold value 2 Delay from 0 t...

Страница 15: ...ching delay from 0 to 1 Input WC 7 5 DPT_TimePeri odSec 2 bytes 129 Coolant temp Switching delay from 1 to 0 Input WC 7 5 DPT_TimePeri odSec 2 bytes 130 Coolant temp Switching output Output R CT 1 1 D...

Страница 16: ...k Output WC 1 2 DPT_Bool 1 bit 150 Logic input 1 Input WC 1 2 DPT_Bool 1 bit 151 Logic input 2 Input WC 1 2 DPT_Bool 1 bit 152 Logic input 3 Input WC 1 2 DPT_Bool 1 bit 153 Logic input 4 Input WC 1 2...

Страница 17: ...1 8 bit output B Output R CT 5 1 byte 185 OR logic 1 Block Input WC 1 1 DPT_Switch 1 bit 186 OR logic 2 1 bit switching output Output R CT 1 2 DPT_Bool 1 bit 187 OR logic 2 8 bit output A Output R CT...

Страница 18: ...ton 3 encoder 8 bit Output R CT 5 10 DPT_Val ue_1_Ucount 1 byte 217 Pushbutton 3 encoder 16 bit Output R CT 9 9 xxx 2 bytes 218 Pushbutton 3 Scene call up Output R CT 18 1 DPT_Scene Control 1 byte 219...

Страница 19: ...T_Start 1 bit 242 Pushbutton 7 switching Output R CT 1 1 DPT_Switch 1 bit 243 Pushbutton 7 dimming Input Output RWCT 3 7 DPT_Con trol_Dimming 4 bit 244 Pushbutton 7 encoder 8 bit Output R CT 5 10 DPT_...

Страница 20: ...hether a plug and contact sensor T NTC ST is connected 2 Whether a circuit board sensor sensor for wall mounting in junction box T UP basic temperature or TH UP basic temperature and air humidity is c...

Страница 21: ...external portion is used all of the following settings are related to the overall read ing Set the send pattern for the reading The minimum and maximum readings can be saved and sent to the bus Using...

Страница 22: ...ew value can be received or simply a command to increase or decrease During initial commissioning a threshold value must be defined which will be valid un til the first call with a new threshold value...

Страница 23: ...ld value 0 50 20 When the following conditions apply the output is TV Threshold value TV above 1 TV Hyst below 0 TV above 0 TV Hyst below 1 TV below 1 TV hysteresis above 0 TV below 0 TV hysteresis ab...

Страница 24: ...d until the first call setting via objects is ignored Behaviour of the switching output On block Do not send message send 0 send 1 On release with 2 seconds release delay Dependent on the Switching ou...

Страница 25: ...you can use three objects with one object switching between eco and standby mode and the two others are used to activate comfort mode or frost heat pro tection mode The comfort object then blocks the...

Страница 26: ...lue only the deviation from the comfort set point value is listed for the other modes e g 2 C less for standby mode Cycle if sent periodically 5 s 5 min 2 h Send status objects on change on change to...

Страница 27: ...setpoint as well as a temperature range in which the setpoint value may be modified If setpoint values are entered separately If the comfort setpoint value is used as a basis If the comfort setpoint v...

Страница 28: ...eduction increment of the value is set Eco setpoint Eco mode is usually used for night mode If setpoint values are entered separately A starting setpoint value is defined as well as a temperature rang...

Страница 29: ...ol variable for heating and cooling If the 2nd level has a common control variable you also determine the control mode of the 2nd level here When using the control variable for a 4 6 way valve the fol...

Страница 30: ...the set point value In case of a short reset time the control responds with a fast increase of the control variable In case of a long reset time the control responds somewhat less urgently and needs l...

Страница 31: ...level 2 2 point control is used for systems which are only set to ON or OFF Enter the hysteresis that prevents frequent on off switching of temperatures in the threshold range Control type PI control...

Страница 32: ...i e above which setpoint value deviation the second level is added PI control with control parameters This setting allows individual input of the parameters for PI control Specify the deviation from t...

Страница 33: ...variable follows the rule again 2 point control only level 2 2 point control is used for systems which are only set to ON or OFF Enter the hysteresis that prevents frequent on off switching of temper...

Страница 34: ...perature and humidity sensor in the General settings Use Offsets to adjust the readings to be sent The unit can calculate a mixed value from its own reading and an external value Set the mixed value c...

Страница 35: ...ter power supply restoration and pro gramming should not be used for the initial start up as the factory settings are always used until the first communication setting via objects is ignored Set the t...

Страница 36: ...in 0 1 RH valid until first communication 1 1000 650 Object value limit min in 0 1 RH 1 1000 Object value limit max in 0 1 RH 1 1000 Type of threshold value change Absolute value Increase decrease Inc...

Страница 37: ...l one or two stage dehumidification or combined humidification dehumidification Use switching output block No Yes Analysis of the blocking object At value 1 block At value 0 release At value 0 block A...

Страница 38: ...is ignored During initial commissioning a setpoint value must be defined which is valid until the first communication of a new setpoint value For units which have already been tak en into service the...

Страница 39: ...r humidification and dehumidifi cation appear level 1 2 For dual level dehumidification the setpoint value difference between the two levels must be defined i e the setpoint value which when exceeded...

Страница 40: ...set the send pattern Activate monitoring of the coolant temperature if required The menus for the further setting of the monitoring are then displayed 5 9 1 Coolant temperature monitoring A threshold...

Страница 41: ...fset will be retained until a new value or a change is transferred The current value is saved so that it is retained in the event of a power supply failure and will be available once the power supply...

Страница 42: ...None 1 s 2 s 5 s 10 s 2 h Switching delay from 1 to 0 for setting via objects valid until 1st communication None 1 s 2 s 5 s 10 s 2 h Switching output sends on change on change to 1 on change to 0 on...

Страница 43: ...settings made for absolute humidity regarding the relevant sensor also apply to the comfort field settings The Interface KNX B8 TH can send a message to the bus if the limits of the comfort field are...

Страница 44: ...hat the control variable comparator should output and activate the input objects to be used Transmission patterns and blocks can also be set Sending pattern never periodically on change on change and...

Страница 45: ...and above change of if sent on change 1 2 5 10 20 25 50 Analysis of the blocking object at value 1 block at value 0 release at value 0 block at value 1 release Blocking object value before 1st communi...

Страница 46: ...t use Logic inputs 1 16 Logic inputs 1 16 inverted all switching events that the device provides see chapter Connection inputs of AND and or OR logic Output type a 1 bit object two 8 bit objects Outpu...

Страница 47: ...n change of logic object receipt and periodically Send cycle if sent periodically 5 s 10 s 2 h Use block No Yes Analysis of the blocking object At value 1 block At value 0 release At value 0 block At...

Страница 48: ...ic input 7 Logic input 7 inverted Logic input 8 Logic input 8 inverted Logic input 9 Logic input 9 inverted Logic input 10 Logic input 10 inverted Logic input 11 Logic input 11 inverted Logic input 12...

Страница 49: ...perature Switching output 6 Temperature inverted Switching output 7 Temperature Switching output 7 Temperature inverted Switching output 8 Temperature Switching output 8 Temperature inverted Switching...

Страница 50: ...same as those of the AND logic In addition the fol lowing inputs are available for the OR logic Switching output AND logic 1 Switching output AND logic 1 inverted Switching output AND logic 2 Switchin...

Страница 51: ...n for button held down set the period be tween button tapped and button held down and what is to take place when the button is pressed and released at different times Function Switch Command when pres...

Страница 52: ...a long button press Command when pressing the pushbutton do not send telegram Command when releasing before time expires Switching Do not send message Command when pressing the button Switching send...

Страница 53: ...ge time difference recall storage and the scenario number 5 14 2 Control modes for drive control If inputs are being used as switches to operate shades or windows then various con trol modes can be se...

Страница 54: ...rive will be positioned resp stopped incrementally If the drive is to be moved a bit farther then a little longer push is needed longer than time 1 but shorter than time 1 2 The drive stops immediatel...

Страница 55: ...ing command Release after time 1 expired but before time 2 expires Stop Release after time 1 2 expired Move into end position Control mode Comfort mode Behavior during button operation Button is pushe...

Страница 56: ...60184 white 60185 60189 black WS1 Style PF 60191 60194 white 60196 60199 black WS1000 Style 60201 60204 white 60206 60209 black WS1000 Style PF 60211 60214 white 60216 60219 black Elsner Elektronik Gm...