POLARIS 10●15●20●30●40●60●80●100●120●160
TRIPHASE-TRIPHASE
Rev. 04 – 06 December 2016
25
APPENDIX 1: SPECIFICATIONS
MODEL
POLARIS
10
POLARIS
15
POLARIS
20
POLARIS
30
POLARIS
40
POLARIS
60
In
p
u
t
Capacity
10KVA
9KW
15KVA
13.5KW
20KVA
18KW
30KVA
27KW
40KVA
36KW
60KVA
54KW
Phase
3 Phase 4 Wires and Ground
Rated Voltage
380/400/415Vac
Voltage Range
208~478Vac
Frequency Range
45-55Hz a 50Hz / 56-66Hz a 60Hz (auto sensing)
Power Factor
≥
0.99
Current THDi
≤
2%(100% non linear load)
Bypass Voltage
Range
Max Voltage.:
25% (op5%,+10%,+15% )
20% (op10%,+15% )
15% (op10% )
Min. Voltage.:
-45% (optional -20%
、
-30%)
Frequency protection range: ±10%
Generator Input
Supported
O
u
tp
u
t
Phase
3 Phase 4 Wires and Ground
Rated Voltage
380/400/415Vac
Power Factor
0.9
Voltage Regulation
±1%
Frequency
Utility
Mode
±1%
、
±2%
、
±4%
、
±5%
、
±10% of the rated frequency (optional)
Battery
Mode
(50/60±0.1%)Hz
Crest Factor
3:1
THD
≤
1% with linear load
≤
3% with non linear load
Efficiency
(in normal mode)
≥
96,5%
≥
97,5%
B
a
tt
e
ry
Voltage
Standard UPS: ±120Vdc (10+10) 12V 7/9AH
Long run backup UPS ±96V/±108V/±120Vdc (16/18/20 pz. optional)
Standard UPS:
±240Vdc
(20+20)
12V 7/9AH
Long run backup
UPS:
±192/±204/±216/
±228/±240Vdc
(32/34/36/38/40
pz optional)
Standard UPS:
±120Vdc
(10+10) 12V
7/9AH
Long run backup
UPS
±96V/±108V/±12
0Vdc (16/18/20
pz. optional)
Charge Current (A)
Charge current is automatically set in according to the capacity and the quantity of the batteries
Standard UPS (20pcs): 1,35A
Standard UPS (2X20pcs): 2,7A
Standard UPS (3X20pcs): 4,5A
Long run backup UPS: max 10A
Battery Test
Supported
Transfer Time
Utility to Battery: 0ms
Utility to bypass: 0ms