POLARIS 10●15●20●30●40●60●80●100●120●160
TRIPHASE-TRIPHASE
Rev. 04 – 06 December 2016
22
ABT
(Automatic Battery Test)
For setup the ABT function is necessary have a password to enter in the setting system menu.
The choices are:
for Test Type:
OFF = No Test
10s
= Test for 10s
10min = Test for 10Min
EOD = Test until End Of Discharge
for Test Circle:
1day to 60days
If the Test Battery fail (MBT/ABT):
-The Ups goes to Bypass
-Battery Led blinking every 1 sec
-Buzzer bip every 1 sec
-Display message: Fault / Battery EOD
If the Test Battery is setting for 10min and backup time is lower than 10 min (MBT/ABT):
- Battery Led blinking
-Display message: Fault / Bat Low pre-warning
-The Ups goes to Inverter mode
-Battery Led blinking every 1 sec
-Buzzer bip every 1 sec
-Display message: Fault / Battery EOD
Until the battery charge percentage reach about 43% then only the green inverter Led is ON
WRONG ROTARY FIELD
(Input main wrong connection)
When you turn On the UPS and the input phase is in wrong connection we have this situation:
-Red Led (fault) blinking every 1 sec
-Yellow Led (bypass) blinking every 1 sec
-Buzzer bip continuous
-Display message: Fault / Bypass not available / INPUT PHASE REVERSE
-Green Led (inverter) on.