24
Cable connection error
Twice per second
Fault LED lit
CAN comm. Fault
Twice per second
Fault LED lit
Parallel load sharing fault
Twice per second
Fault LED lit
Battery over voltage
Once per second
Fault LED blinking
Mains Site Wiring Fault
Once per second
Fault LED blinking
Bypass Site Wiring Fault
Once per second
Fault LED blinking
Output Short-circuit
Once per second
Fault LED blinking
Rectifier over current
Once per second
Fault LED blinking
Bypass over current
Once per second
BPS LED blinking
Overload
Once per second
INV or BPS LED blinking
No battery
Once per second
Battery LED blinking
Battery under voltage
Once per second
Battery LED blinking
Battery low pre-warning
Once per second
Battery LED blinking
Internal Communication Error
Once per 2 seconds
Fault LED blinking
DC component over limit.
Once per 2 seconds
INV LED blinking
Parallel Overload
Once per 2 seconds
INV LED blinking
Mains volt. Abnormal
Once per 2 seconds
Battery LED lit
Mains freq. abnormal
Once per 2 seconds
Battery LED lit
Bypass Not Available
BPS LED blinking
Bypass unable to trace
BPS LED blinking
Inverter on invalid
Reserve
inverter not on
4.6 Options
SNMP card: internal SNMP / external SNMP
◆
Loosen the 2 torque screws (on each side of the card).
◆
Carefully pull out the card. Reverse the procedure for re-installation
The slot called SNMP supports the MEGAtec protocol. We advise that NetAgent II-3 port is also a tool to
remotely monitor and manage any UPS system
NetAgent II-3Ports supports the Modem Dial-in (PPP) function to enable the remote control via the
internet when the network is unavailable.
In addition to the features of a standard NetAgent Mini, NetAgent II has the option to add NetFeeler Lite
to detect temperature, humidity, smoke and security sensors. Thus, making NetAgent II a versatile
management tool. NetAgent II also supports multiple languages and is setup for web-based auto
language detection.
RELAY card
Dry contact card provide dry contacts for UPS external monitoring, and tell the UPS operation status.
Dry contact card provide 10 connectors for users, 7 outputs for indicating UPS status, 1 for common
ground, 2 input for remote UPS shut down.
SNMP Card
RELAY Card