Click the button “Append”, then the connection between UPS & computer is accomplished.
CAUTION!
When the UPS worked on inverter. If you want to use PC to set the output voltage and frequency.
Must shut down the inverter first
4. OPERATION
4.1 Operation Modes
The UPS is a double-conversion on-line UPS that may operate in the following alternative modes:
◆
Normal mode
The rectifier/charger derives power from the AC Mains and supplies DC power to the inverter while
floating and boosting charge the battery simultaneously. Then, the inverter converts the DC power to AC
and supplies to the load.
◆
Battery mode (Stored Energy Mode)
If the AC mains input power fails, the inverter, which obtains power from the battery, supplies the critical
AC load. There is no power interruption to the critical load. The UPS will automatically return to Normal
Mode when AC recovers.
◆
Bypass mode
If the inverter is out of order, or if overload occurs, the static transfer switch will be activated to transfer
the load from the inverter supply to bypass supply without interruption to the critical load. In the event
that the inverter output is not synchronized with the bypass AC source, the static switch will perform a
transfer of the load from the inverter to the bypass with power interruption to the critical AC load. This is
to avoid paralleling of unsynchronized AC sources. This interruption is programmable but typically set to
be less than an electrical cycle e.g. less than 15ms (50Hz) or less than 13.33ms (60Hz).
◆
◆
◆
◆
ECO Mode
When the UPS is at AC Mode and the requirement to the load is not critical, the UPS can be set at
ECO mode in order to increase the efficiency of the power supplied. At ECO mode, the UPS works
at Line-interactive mode, so the UPS will transfer to bypass supply. When the AC is out of set
window, the UPS will transfer from bypass to Inverter and supplies power from the battery, and then
the LCD shows all related information on the screen.
◆
Parallel redundancy mode (system expansion)
To achieve a higher capacity and / or increase reliability, the outputs of up to four UPS can be
programmed to operate in parallel and the built-in parallel controller in each UPS ensures automatic load
sharing.
◆
Maintenance mode (Manual Bypass)
A manual bypass switch is available to ensure continuity of supply to the critical load when the UPS is
out of order or in repair and this manual bypass switch bears for equivalent rated load.
4.2 Turn on/off UPS
4.2.1
Start procedure with Main present
CAUTION!
Make sure grounding is properly done!