Menu 9 – Motor 1 Obstruction Detect Margins
This sets the current sensitivity margin above the normal run current to trip the gate if an obstruction is
detected. Different obstruction margins can be set for the open and close direction. Also the response
time is adjustable.
The minimum margin will allow least pressure applied to trip the gate if it hits an object. The maximum
margin will allow for a large amount of pressure applied to trip the gate if it hits an object.
Menu No.
Motor 1 Obstruction Detect Margins
and Response Time
Factory Default
Adjustable
9.1
Open Obstruction Margin
1 Amp
0.2 - 6.0 Amps
9.2
Close Obstruction Margin
1 Amp
0.2 - 6.0 Amps
9.3
Open and Close Slow Speed
Obstruction Margin
1 Amp
0.2 - 6.0 Amps
9.4
Obstruction Detect Response Time
Medium
Fast, Medium, Slow
and Very Slow
9.5
Exit
Margin Example
Motor is running at 2 Amps and the margin is set to 1.5 Amps, an obstruction detect will occur at
3.5 Amps (Normal Running C Margin).
For high margin settings the supply transformer should be large enough to supply the high margin
current.
If the gate hits an object on closing it will automatically stop and then re-open. If the gate hits an object
on opening it will automatically stop.
24
Double Gate & Door Controller
with Eclipse
®
Operating System (EOS)