Strobe (Warning) Light when Opening or Closing
The relay output is activated whenever the gate are operating. The factory default is Off. Either output
1 or output 2 can be changed to strobe (Warning) light. Both relay outputs are voltage-free contacts.
Having it voltage-free allows you to connect either 12VDC/AC, 24VDC/AC or 240VAC supply to the
common to power the strobe light. Then the normally open contact drives the light. See diagram above.
Relay
R
e
c
e
i
v
e
r
Master Control
Output 2 C
Output 2 NC
Output 2 NO
+
-
Unfiltered DC Output
Output voltage depends
on supply voltage
+ if DC
- if DC
240VAC supply
24VAC/DC or
Depends on the light
12VAC/DC
Locking Actuator
Locking actuator mode uses both relay output 1 and relay output 2. The 2 outputs are used to change
the polarity of the locking actuator to lock and unlock during opening and closing cycle. During pre-
open relay output 1 is “ON” and during post-close relay output 2 is “ON”. Pre-open and post-close
times are adjustable.
Gate Open
The relay output is activated whenever the gate is not fully closed. The factory default is Off. Either
output 1 or output 2 can be changed to gate open.