Manual R2000-43-E             Release: 1.03                © Elotech GmbH                          Page 11/24 

X. 

Operating Levels 

 

The operation of the controller is divided into 3 levels. 
 
After switching on the unit, it will be automatically in the operating level. 
 
 
 
 
 

 

 

 

    and 

 

 

 

 

and 

 
 
 

 

 

 

   press   

 

 

      press appr. 5 sec. 

 
 

 

 

 

 

 

Parameter- 

 

 

Configuration- 

Controller:         Operating level 

 

 

    level   

 

 

       level 

“on“ 
 

             process value 

 

              Y  ( output ratio ) 

 

 

Zone : on / OFF 

 

 

(process) 

 

            setpoint value 

 

 

     (set) 

 

 

 

 

 

 

       Y 

 

 

 

         ConF 

 
 

 

 

 

 

 

    1Y.Hi   

 

 

          SEn 

 
 
 
 
 

 

Alarm A1 

 

 

Alarm A2  

 

 

     OFSt   

 

 

        COPY 

 
 
 
 
 
 

 

 

 

 

                Back into the operation level: 

 
 

 

 

       

 

 - Press   

     1 sec.      or        automatically after appr. 30 sec.  

 
 

Operating level

 (for each zone separatly): 

Process- and Setpoint value will be displayed simultaneously.  Within the operating level the setpoint can be adjusted 
by pressing the  " up " / " down "  - keys. 
Every adjustment has to be quit by pressing the  „ E “ -  key. 
All parameters within the operating level ( including the alarm values ) can , in succession, be displayed by pressing the 
„ “ - key and adjusted by pressing the  " up " / " down " - keys.  Quit by pressing the  „ E “ -  key. 
 

Parameter level

 (for each zone separatly): 

Within the parameter level the values are adjusted to suit each individual process. 
This level is reached by simultaneously pressing the  "P" - and " E " -keys. 
The display of each single parameter within the parameter level and their adjustment, are made in the same way as 
within the operating level. 
After either pressing the „E“ - key for approx. 1 second, or waiting for a period of  approx. 30 seconds, 
the unit will automatically return to the operating level (display of process value and setpoint). 
 

Configuration level: 

This primary informations have to be entered before taking the instrument into operation. 

The configuration level is reached by simultaneously pressing the  "P" - and " E " - keys for a period of approx. 5 seconds. 
First choose the configuration level in zone 0. Here general settings have to be made. 
This has to be programmed at first: 
- Only TC- or RTD-connection for all zones?    Or: Mixed connection ? 
- Alarm configuration (valid for all zones)      

 

- Function of key „F1“ 

- Software key 

 

 

 

 

- Serial interface informations 

- Heater current monitoring 
 
Than choose the configuration level of each individual controller zone. 
This has to be programmed at second: 
- Controller type 

 

 

(for each zone) 

- Input type (sensor type), sensor range (for each zone) 
- Min. and max. setpoint range  

(for each zone) 

The display of each single parameter within the configuration level and their adjustment, made in the same fashion as within 
the operating level. 
There is also a copy function available. So it is possible, to copy the programmed parameters of one zone to other zones. 
After either pressing the „E“ - key for approx. 1 second, or waiting for a period of  approx. 30 seconds, 
the unit will automatically return to the operating level (display of process value and setpoint). 

 P 
PP

E 

 E 

  P 

 P 

 P 

 P 

 P 
PP

E 

 P 

 P 

Содержание R 2000 - 431

Страница 1: ...ontroller Heater Current Monitoring Option CANopen Interface Option 2 x Analog input 0 10VDC Option Format 96 x 96 mm 1 4 DIN Installation depth 122 mm DESCRIPTION AND OPERATING MANUAL I ELOTECH Indus...

Страница 2: ...ation Instructions 24 Please read this operating manual before starting up carefully Observe the installation and connecting instructions Note Only trained personnel following the regional safety regu...

Страница 3: ...erface 5 with heater current monitoring Only with bistable voltage outputs Codes 432 436 437 0 sensor programmable RTD Pt100 DIN 2 or 3 wire Type L Type J Type K 431 4 zones heat only or heating off c...

Страница 4: ...roller Control output OUT 1 Zone 1 heating or cooling heating to OUT 4 Zone 4 heating or cooling heating Control output OUT 5 Zone 1 cooling to OUT 8 Zone 4 cooling Alarm Output A1 Alarm 1 Temperature...

Страница 5: ...Control output OUT 1 Zone 1 heating or cooling heating to OUT 4 Zone 4 heating or cooling heating Control output OUT 5 Zone 1 cooling to OUT 8 Zone 4 cooling Alarm Output A1 Alarm 1 Temperature or he...

Страница 6: ...Control output OUT 1 Zone 1 heating or cooling heating to OUT 4 Zone 4 heating or cooling heating Control output OUT 5 Zone 1 cooling to OUT 8 Zone 4 cooling Alarm Output A1 Alarm 1 Temperature or he...

Страница 7: ...controller Control output OUT 1 Zone 1 heating or cooling heating to OUT 4 Zone 4 heating or cooling heating Control output OUT 5 Zone 1 cooling to OUT 8 Zone 4 cooling Alarm Output A1 Alarm 1 Temper...

Страница 8: ...controller Control output OUT 1 Zone 1 heating or cooling heating to OUT 4 Zone 4 heating or cooling heating Control output OUT 5 Zone 1 cooling to OUT 8 Zone 4 cooling Alarm Output A1 Alarm 1 Temper...

Страница 9: ...nning When the parameter adjustments have been altered but not entered the display will flash bright dark E Confirmation and storage of the pre selected values The display will show a light chain as a...

Страница 10: ...e high temperature X 0 5 W SP temperature o k low temperature X 0 5 W SP Zone Zone Zone Zone 1 2 3 4 The displayed dec point shows the heating or cooling on off off off actual situation of the control...

Страница 11: ...ing level After either pressing the E key for approx 1 second or waiting for a period of approx 30 seconds the unit will automatically return to the operating level display of process value and setpoi...

Страница 12: ...usted and displayed relative to the setpoint deviation alarm as an absolute value LED Switching behaviour Configuration LED Switching behaviour Configuration off on 1 off on 2 8 on off 4 on off 5 9 se...

Страница 13: ...ameter Co A1 to number 8 or 9 Heater current monitoring via relay A2 Program parameter Co A2 to number 8 or 9 The heater current to be monitored has to be programed as an absolute value into the opera...

Страница 14: ...temperature indications Display indication in this case Comparable with temperature too high But there is no special indication via tendency or alarm status display Display C 0 2 Er Cu PROCESS PROCESS...

Страница 15: ...Gateway 8n2 8 data none 2 stopbit bAud Baud rate OFF 0 3 9 6 kBaud The baud rate denotes the transmission rate at which one bit is transmitted InterBus S Gateway 9 6 kBaud Details see sep interface de...

Страница 16: ...S 32 2912 F If the Sensor selection is changed the following parameters will be set as follows and need to be re adjusted Setpoint 1 setpoint 2 SP Lo Process value offset OFF Lower setpoint limitatio...

Страница 17: ...ults in a slower more regular heating period For this purpose the bistable voltage output must be taken that actuates SSR relays If the softstart is active the controllers autotune function can t oper...

Страница 18: ...sensor break was 100 if the controller is working along a setpoint ramp if the control deviation was more than 0 25 of the total range at the time of sensor break if th prop band P xp 0 if the soft st...

Страница 19: ...i output ratio limit 0 100 ex works 100 cooling 1 P heating OFF 0 1 100 0 ex works 3 0 prop band P If 1 P OFF control action on off without feedback next parameter 1 Sd 1 d heating OFF 1 200 secs ex w...

Страница 20: ...utputs is not possible 2 P cooling OFF 0 1 100 0 ex works 3 0 prop band P If 2 P OFF control action on off without feedback next parameter 2 Sd 2 d cooling OFF 1 200 secs ex works 30 rate D 2 J coolin...

Страница 21: ...n The tuning algorithm can be activated at any time by selecting the OPT on and pressing the E key Zone display During self tuning OPt is shown in the display alternating with the setpoint value Tende...

Страница 22: ...d setpoint If the ramp is active the corresponding LED lights up on the faceplate The ramp can be activated for both setpoint1 and setpoint2 By programming the second setpoint accordingly a setpoint p...

Страница 23: ...ested according to 2004 108 EC EN 61326 1 industrial areas Electr safety EN 61010 1 Power supply Standard 230 V AC 10 48 62 Hz appr 10VA Connections Screw terminals Protection mode IP 20 DIN 40050 Ins...

Страница 24: ...in control panels The controller must be installed so that it is protected against impermissible humidity and severe contamination In addition make sure that the permitted ambient temperature is not e...

Отзывы: