Manual R2000-43-E Release: 1.03 © Elotech GmbH Page 11/24
X.
Operating Levels
The operation of the controller is divided into 3 levels.
After switching on the unit, it will be automatically in the operating level.
and
and
press
press appr. 5 sec.
Parameter-
Configuration-
Controller: Operating level
level
level
“on“
process value
Y ( output ratio )
Zone : on / OFF
(process)
setpoint value
(set)
Y
ConF
1Y.Hi
SEn
Alarm A1
Alarm A2
OFSt
COPY
Back into the operation level:
- Press
1 sec. or automatically after appr. 30 sec.
Operating level
(for each zone separatly):
Process- and Setpoint value will be displayed simultaneously. Within the operating level the setpoint can be adjusted
by pressing the " up " / " down " - keys.
Every adjustment has to be quit by pressing the „ E “ - key.
All parameters within the operating level ( including the alarm values ) can , in succession, be displayed by pressing the
„ P “ - key and adjusted by pressing the " up " / " down " - keys. Quit by pressing the „ E “ - key.
Parameter level
(for each zone separatly):
Within the parameter level the values are adjusted to suit each individual process.
This level is reached by simultaneously pressing the "P" - and " E " -keys.
The display of each single parameter within the parameter level and their adjustment, are made in the same way as
within the operating level.
After either pressing the „E“ - key for approx. 1 second, or waiting for a period of approx. 30 seconds,
the unit will automatically return to the operating level (display of process value and setpoint).
Configuration level:
This primary informations have to be entered before taking the instrument into operation.
The configuration level is reached by simultaneously pressing the "P" - and " E " - keys for a period of approx. 5 seconds.
First choose the configuration level in zone 0. Here general settings have to be made.
This has to be programmed at first:
- Only TC- or RTD-connection for all zones? Or: Mixed connection ?
- Alarm configuration (valid for all zones)
- Function of key „F1“
- Software key
- Serial interface informations
- Heater current monitoring
Than choose the configuration level of each individual controller zone.
This has to be programmed at second:
- Controller type
(for each zone)
- Input type (sensor type), sensor range (for each zone)
- Min. and max. setpoint range
(for each zone)
The display of each single parameter within the configuration level and their adjustment, made in the same fashion as within
the operating level.
There is also a copy function available. So it is possible, to copy the programmed parameters of one zone to other zones.
After either pressing the „E“ - key for approx. 1 second, or waiting for a period of approx. 30 seconds,
the unit will automatically return to the operating level (display of process value and setpoint).