Manual R2000-43-E             Release: 1.03                © Elotech GmbH                          Page 15/24 

Display   

Parameter- 

 

 

Parameter value  

„Process"     

description 

 

 

Display „Set“ 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 
 
 
The following parameters are only valid, if the unit is equipped with a serial interface. 
RS232, RS485, 0/20mA. 
 
Prot 

 

Protocol preselection 

ELO 

 

ELOTECH- standard protocol 

 

 

 

 

 

IbS 

 

Gateway-protocol valid for Profibus-DP,  InterBus-S 

 

 

 

 

 

 

 

Only with RS 485-interface (Code-No.: 4). 

 
Adr 

 

Unit adress 

 

1 .... 255   

(ex works: 1) 

 

 

 

 

 

The computer adresses the unit/controller at this adress. 

 

 

 

 

 

Each unit has ist own adress. With RS-485 it is possible to adress 32 units. 

 
For 

Data format 

7E1 

7 data, even,   1 stopbit 

 

 

7o1 

7 data, odd,  

1 stopbit 

 

 

7E2 

7 data, even,   2 stopbit 

 

 

7o2 

7 data, odd,  

2 stopbit 

 

 

7n2 

7 data, none,   2 stopbit 

 

 

8E1 

8 data, even,   1 stopbit 

 

 

8o1 

8 data, odd,  

1 stopbit 

 

 

8n1 

8 data, none,   1 stopbit         InterBus-S Gateway 

 

 

8n2 

8 data, none,   2 stopbit 

 
bAud 

 

Baud rate 

 

OFF; 0,3 ... 9,6 kBaud 

 

 

 

 

 

The baud rate denotes the transmission rate at which one bit is transmitted. 

 

 

 

 

 

InterBus-S Gateway = 9,6 kBaud 

 
Details, see:   

- sep. interface description: ELOTECH – standard-protocol 

 

 

- sep. interface description: Gateway: M-IBS-5 

 

 

- Download: www.elotech.de 

 

 
 
 
The following parameters are only valid, if the unit is equipped with a CAN interface.  
 
Adr 

 

Unit adress 

 

1 .... 127   

 

 

 

(ex works: 1) 

 
 
bAud 

 

Baud rate 

 

10, 20, 50, 100, 125, 250, 500 kBaud, 1MBaud   (ex works: 20) 

 
 

 

CANopen-specfication: 

CANopen Master:   

no 

 

 

 

 

 

CANopen Slave: 

 

yes 

 

 

 

 

 

Extended Boot-up:   

no 

 

 

 

 

 

Minimum Boot-up:   

yes 

 

 

 

 

 

COB ID Distribution: 

yes; default via SDO 

 

 

 

 

 

Node ID Distribution: 

no;   via device keyboard 

 

 

 

 

 

No. of POD´s: 

 

0RX, 1TX 

 

 

 

 

 

PDO Modes: 

 

async. 

 

 

 

 

 

Variable PDO mapping: 

no 

 

 

 

 

 

Emergency message: 

yes 

 

 

 

 

 

Life guarding: 

 

yes 

 

 

 

 

 

No. of SDO`s: 

 

1RX, 1TX 

 

 

 

 

 

Device Profile: 

 

CiA DS-404 

 
Details, see: 

- CANopen Device Profile CiA  DS-404; ELOTECH Object Dictionary 

 

 

- Download: www.elotech.de 

 
 
 
 
 
20xx 
EL.xx 

 

Control number 

 

No function. End of configuration level 

Содержание R 2000 - 431

Страница 1: ...ontroller Heater Current Monitoring Option CANopen Interface Option 2 x Analog input 0 10VDC Option Format 96 x 96 mm 1 4 DIN Installation depth 122 mm DESCRIPTION AND OPERATING MANUAL I ELOTECH Indus...

Страница 2: ...ation Instructions 24 Please read this operating manual before starting up carefully Observe the installation and connecting instructions Note Only trained personnel following the regional safety regu...

Страница 3: ...erface 5 with heater current monitoring Only with bistable voltage outputs Codes 432 436 437 0 sensor programmable RTD Pt100 DIN 2 or 3 wire Type L Type J Type K 431 4 zones heat only or heating off c...

Страница 4: ...roller Control output OUT 1 Zone 1 heating or cooling heating to OUT 4 Zone 4 heating or cooling heating Control output OUT 5 Zone 1 cooling to OUT 8 Zone 4 cooling Alarm Output A1 Alarm 1 Temperature...

Страница 5: ...Control output OUT 1 Zone 1 heating or cooling heating to OUT 4 Zone 4 heating or cooling heating Control output OUT 5 Zone 1 cooling to OUT 8 Zone 4 cooling Alarm Output A1 Alarm 1 Temperature or he...

Страница 6: ...Control output OUT 1 Zone 1 heating or cooling heating to OUT 4 Zone 4 heating or cooling heating Control output OUT 5 Zone 1 cooling to OUT 8 Zone 4 cooling Alarm Output A1 Alarm 1 Temperature or he...

Страница 7: ...controller Control output OUT 1 Zone 1 heating or cooling heating to OUT 4 Zone 4 heating or cooling heating Control output OUT 5 Zone 1 cooling to OUT 8 Zone 4 cooling Alarm Output A1 Alarm 1 Temper...

Страница 8: ...controller Control output OUT 1 Zone 1 heating or cooling heating to OUT 4 Zone 4 heating or cooling heating Control output OUT 5 Zone 1 cooling to OUT 8 Zone 4 cooling Alarm Output A1 Alarm 1 Temper...

Страница 9: ...nning When the parameter adjustments have been altered but not entered the display will flash bright dark E Confirmation and storage of the pre selected values The display will show a light chain as a...

Страница 10: ...e high temperature X 0 5 W SP temperature o k low temperature X 0 5 W SP Zone Zone Zone Zone 1 2 3 4 The displayed dec point shows the heating or cooling on off off off actual situation of the control...

Страница 11: ...ing level After either pressing the E key for approx 1 second or waiting for a period of approx 30 seconds the unit will automatically return to the operating level display of process value and setpoi...

Страница 12: ...usted and displayed relative to the setpoint deviation alarm as an absolute value LED Switching behaviour Configuration LED Switching behaviour Configuration off on 1 off on 2 8 on off 4 on off 5 9 se...

Страница 13: ...ameter Co A1 to number 8 or 9 Heater current monitoring via relay A2 Program parameter Co A2 to number 8 or 9 The heater current to be monitored has to be programed as an absolute value into the opera...

Страница 14: ...temperature indications Display indication in this case Comparable with temperature too high But there is no special indication via tendency or alarm status display Display C 0 2 Er Cu PROCESS PROCESS...

Страница 15: ...Gateway 8n2 8 data none 2 stopbit bAud Baud rate OFF 0 3 9 6 kBaud The baud rate denotes the transmission rate at which one bit is transmitted InterBus S Gateway 9 6 kBaud Details see sep interface de...

Страница 16: ...S 32 2912 F If the Sensor selection is changed the following parameters will be set as follows and need to be re adjusted Setpoint 1 setpoint 2 SP Lo Process value offset OFF Lower setpoint limitatio...

Страница 17: ...ults in a slower more regular heating period For this purpose the bistable voltage output must be taken that actuates SSR relays If the softstart is active the controllers autotune function can t oper...

Страница 18: ...sensor break was 100 if the controller is working along a setpoint ramp if the control deviation was more than 0 25 of the total range at the time of sensor break if th prop band P xp 0 if the soft st...

Страница 19: ...i output ratio limit 0 100 ex works 100 cooling 1 P heating OFF 0 1 100 0 ex works 3 0 prop band P If 1 P OFF control action on off without feedback next parameter 1 Sd 1 d heating OFF 1 200 secs ex w...

Страница 20: ...utputs is not possible 2 P cooling OFF 0 1 100 0 ex works 3 0 prop band P If 2 P OFF control action on off without feedback next parameter 2 Sd 2 d cooling OFF 1 200 secs ex works 30 rate D 2 J coolin...

Страница 21: ...n The tuning algorithm can be activated at any time by selecting the OPT on and pressing the E key Zone display During self tuning OPt is shown in the display alternating with the setpoint value Tende...

Страница 22: ...d setpoint If the ramp is active the corresponding LED lights up on the faceplate The ramp can be activated for both setpoint1 and setpoint2 By programming the second setpoint accordingly a setpoint p...

Страница 23: ...ested according to 2004 108 EC EN 61326 1 industrial areas Electr safety EN 61010 1 Power supply Standard 230 V AC 10 48 62 Hz appr 10VA Connections Screw terminals Protection mode IP 20 DIN 40050 Ins...

Страница 24: ...in control panels The controller must be installed so that it is protected against impermissible humidity and severe contamination In addition make sure that the permitted ambient temperature is not e...

Отзывы: