Display 

Parameter 

 

Display  

"Process" 

 

 

„Set“ 

 

 

 

 

 

 

 

 

 

 

 

 

 

 
 

Softstart-function 

 
 

 

TAKE CARE:  

If you take the softstart-function, make sure that the heating control outputs are  
equipped with bistable voltage (logic) outputs.  
This function is not allowed for instruments with relay-outputs 
(in this case set So.St = OFF).  
Otherwise the relais will be destroid becuse they switch too fast.  

 

Softstart (general function): 

 

 

 

During the softstart the controllers’ heating output response is limited to a pre-selected ratio, in order 

 

 

 

to achieve a slow baking out of high performance heat cartridges. 

 

 

 

Simultaneously the output clock frequency is quadrupled. Once the process value reaches 

 

 

 

the softstart setpoint, it remains stable at this value for a pre-selcted hold-duration time. 

 

 

 

At the end of this period the process value rises to the valid setpoint. 

 

 

 

This results in a slower, more regular heating period. 

 

 

 

For this purpose the bistable voltage output must be taken, that actuates SSR relays. 

 

 

 

If the softstart is active, the controllers’ autotune function can’t operated (Er.OP). 

 

 

 

If a setpoint-ramp has been programmed, the softstart has priority, and the ramp will only 

 

 

 

become active after the softstart has been completed. 

 
 

 

 

The softstart only works, 
- if the parameter  „1  P“  (prop. band, xp) is programmed > 0,1%. 

 

 

 

- if the actual process value is lower than So.SP – 5% of the selected measuring range. 

 
 

 

 

It is possible, to select this function for each zone individally. 

 
 
 
 

 

 

 

Setpoint SP 

 
 
 
 
 

 

 

 

        So.SP 

 

 

 

        Softstart setpoint 

 
 

 

 

 

 

          So. Y 

 

 

 

 

 

 

 

 

So.ti 

 
 

 

 

 

 

 

 

 

 

 

 

 

 

   t 

 
 
 
So.St 

 

Softstart-function   

OFF: 

Softstart not active  (ex works) 

 

 

 

 

 

 

Next parameter  So.Y, So.SP, So.ti are not shown. 

 

 

 

 

 

On: 

Softstart in action. 

 

 

 

 

 

 

The softstart function always runs, if the controller is switched on and / or 

 

 

 

 

 

 

if the actual temperature is below  the softstart setpoint So.SP minus 5% 

 

 

 

 

 

 

of the range (e.g. range: 400^C -> 5%= 20°C).   

 
So. Y 

 

Softstart output ratio 

10 ... 100% 

 
So.SP 

 

Softstart setpoint   

range: SP.Lo .... SP.Hi 

 
So.ti 

 

Softstart duration time 

OFF;  0,1 ... 10,0 min. 

 

Содержание R 2000 - 431

Страница 1: ...ontroller Heater Current Monitoring Option CANopen Interface Option 2 x Analog input 0 10VDC Option Format 96 x 96 mm 1 4 DIN Installation depth 122 mm DESCRIPTION AND OPERATING MANUAL I ELOTECH Indus...

Страница 2: ...ation Instructions 24 Please read this operating manual before starting up carefully Observe the installation and connecting instructions Note Only trained personnel following the regional safety regu...

Страница 3: ...erface 5 with heater current monitoring Only with bistable voltage outputs Codes 432 436 437 0 sensor programmable RTD Pt100 DIN 2 or 3 wire Type L Type J Type K 431 4 zones heat only or heating off c...

Страница 4: ...roller Control output OUT 1 Zone 1 heating or cooling heating to OUT 4 Zone 4 heating or cooling heating Control output OUT 5 Zone 1 cooling to OUT 8 Zone 4 cooling Alarm Output A1 Alarm 1 Temperature...

Страница 5: ...Control output OUT 1 Zone 1 heating or cooling heating to OUT 4 Zone 4 heating or cooling heating Control output OUT 5 Zone 1 cooling to OUT 8 Zone 4 cooling Alarm Output A1 Alarm 1 Temperature or he...

Страница 6: ...Control output OUT 1 Zone 1 heating or cooling heating to OUT 4 Zone 4 heating or cooling heating Control output OUT 5 Zone 1 cooling to OUT 8 Zone 4 cooling Alarm Output A1 Alarm 1 Temperature or he...

Страница 7: ...controller Control output OUT 1 Zone 1 heating or cooling heating to OUT 4 Zone 4 heating or cooling heating Control output OUT 5 Zone 1 cooling to OUT 8 Zone 4 cooling Alarm Output A1 Alarm 1 Temper...

Страница 8: ...controller Control output OUT 1 Zone 1 heating or cooling heating to OUT 4 Zone 4 heating or cooling heating Control output OUT 5 Zone 1 cooling to OUT 8 Zone 4 cooling Alarm Output A1 Alarm 1 Temper...

Страница 9: ...nning When the parameter adjustments have been altered but not entered the display will flash bright dark E Confirmation and storage of the pre selected values The display will show a light chain as a...

Страница 10: ...e high temperature X 0 5 W SP temperature o k low temperature X 0 5 W SP Zone Zone Zone Zone 1 2 3 4 The displayed dec point shows the heating or cooling on off off off actual situation of the control...

Страница 11: ...ing level After either pressing the E key for approx 1 second or waiting for a period of approx 30 seconds the unit will automatically return to the operating level display of process value and setpoi...

Страница 12: ...usted and displayed relative to the setpoint deviation alarm as an absolute value LED Switching behaviour Configuration LED Switching behaviour Configuration off on 1 off on 2 8 on off 4 on off 5 9 se...

Страница 13: ...ameter Co A1 to number 8 or 9 Heater current monitoring via relay A2 Program parameter Co A2 to number 8 or 9 The heater current to be monitored has to be programed as an absolute value into the opera...

Страница 14: ...temperature indications Display indication in this case Comparable with temperature too high But there is no special indication via tendency or alarm status display Display C 0 2 Er Cu PROCESS PROCESS...

Страница 15: ...Gateway 8n2 8 data none 2 stopbit bAud Baud rate OFF 0 3 9 6 kBaud The baud rate denotes the transmission rate at which one bit is transmitted InterBus S Gateway 9 6 kBaud Details see sep interface de...

Страница 16: ...S 32 2912 F If the Sensor selection is changed the following parameters will be set as follows and need to be re adjusted Setpoint 1 setpoint 2 SP Lo Process value offset OFF Lower setpoint limitatio...

Страница 17: ...ults in a slower more regular heating period For this purpose the bistable voltage output must be taken that actuates SSR relays If the softstart is active the controllers autotune function can t oper...

Страница 18: ...sensor break was 100 if the controller is working along a setpoint ramp if the control deviation was more than 0 25 of the total range at the time of sensor break if th prop band P xp 0 if the soft st...

Страница 19: ...i output ratio limit 0 100 ex works 100 cooling 1 P heating OFF 0 1 100 0 ex works 3 0 prop band P If 1 P OFF control action on off without feedback next parameter 1 Sd 1 d heating OFF 1 200 secs ex w...

Страница 20: ...utputs is not possible 2 P cooling OFF 0 1 100 0 ex works 3 0 prop band P If 2 P OFF control action on off without feedback next parameter 2 Sd 2 d cooling OFF 1 200 secs ex works 30 rate D 2 J coolin...

Страница 21: ...n The tuning algorithm can be activated at any time by selecting the OPT on and pressing the E key Zone display During self tuning OPt is shown in the display alternating with the setpoint value Tende...

Страница 22: ...d setpoint If the ramp is active the corresponding LED lights up on the faceplate The ramp can be activated for both setpoint1 and setpoint2 By programming the second setpoint accordingly a setpoint p...

Страница 23: ...ested according to 2004 108 EC EN 61326 1 industrial areas Electr safety EN 61010 1 Power supply Standard 230 V AC 10 48 62 Hz appr 10VA Connections Screw terminals Protection mode IP 20 DIN 40050 Ins...

Страница 24: ...in control panels The controller must be installed so that it is protected against impermissible humidity and severe contamination In addition make sure that the permitted ambient temperature is not e...

Отзывы: