background image

 

 

Technical Support: +44(0)23 9269 6638 (option 3) 

  PAK200574_01K May  2016                       ©2016 ELMDENE INTERNATIONAL LTD  

 
Fault Diagnostic table – Internal - Engineer 

Orange LED 

Diagnostic 

Green LED 

Mains 

Condition 

Possible Cause 

Action 

O

FF

 

O

N

 

Normal 

operation 

Mains present 
Battery fully charged 

None 

O

FF

 

Standby 

Operation 

Mains Lost. No faults present 
Battery driving load 

Investigate loss of mains 

F

LASH 

C

ONTINUOUS

 

O

N

 or O

FF

 

No output 

Output fuse blown 
Output overload 
Output short circuit 

Check and replace 
output fuse 
Disconnect output load 
and test load 

1

 

P

ULSE

 

O

N

 

Battery 

Charging 

No faults active 
Battery charging normally 
but  
< 90% of full charge 

None 

2

 

P

ULSES

 

O

N

 

No Battery 

Battery disconnected 
Battery fuse blown 
Battery heavily discharged 

Check battery 
connections 
Check battery fuse 
Check battery condition 
Replace battery if aged 

O

FF

 

Low Battery 

Volts 

Standby Mode 
Battery almost discharged 

Restore mains 

3

 

P

ULSES

 

O

N

 or O

FF

 

Battery Fault 

High impedance in battery 
connection 
Battery internal fault 

Check battery 
connections for 
corrosion. Replace 
battery if aged 

4

 

P

ULSES

 

O

N

 or O

FF

 

Charger Fault 

Internal failure of battery 
charger 

Return to manufacturer 

5

 

P

ULSES

 

O

N

 or O

FF

 

Battery 

Temperature 

Probe Fault 

Battery temperature monitor 
disconnected or damaged 
PSU running in Safe Mode  

Check temperature 
sensor connections and 
condition of sensor. 
Replace if suspect 

O

C

ONTINUOUS

 

O

N

 or O

FF

 

Internal Fault 

Software fault detected 
PSU running in Safe Mode 

Return to manufacturer 

 

I

NSTALLATION 

 

 

 

This unit is only suitable for installation as permanently connected equipment. The PSU is NOT SUITABLE for 
external installation. This product (PSE) is designed for the use in automatic fire detection and fire alarm systems. If 
it is used as power supply equipment for control and indicating equipment, the PSE shall be installed no further 
than 10cm from the CIE, and close coupled by conduit. 

 

This unit must be fed from a mains power source having a separate (approved) disconnect device and fitted with a 
fuse or other over-current protection device rated at 5 A maximum. Ensure that the disconnect device used has 
appropriate earth fault protection to the applicable standard. 

 

Where the PSU is used to provide power to a fire alarm circuit, the mains isolation and disconnect device should be 
provided solely for this purpose and be suitably marked “FIRE ALARM – DO NOT TURN OFF”. All cabling should meet 
national and local fire system installation regulations, e.g. FP200 type cable for high integrity installations. 

 

Where the PSU is used for other applications, it should be installed according to all relevant safety regulations 
applicable to that application. 

 

Содержание BATT-BOX-65

Страница 1: ...volt free solid state relay fault output signal i loss of mains and ii battery fault charger fault and loss of output In addition there is an RS232 serial interface that can provide diagnostic and fau...

Страница 2: ...A 7 5 A 10 0 A 7 2 A 6 5 A Battery Capacity eg PowerSonic model Yuasa model Interlogix model 2 x 17 18Ah 12 V PS12170 NP17 12 BS131N 2 x 38 Ah 12 V PS12380 NP38 12 2 x 65 Ah 12 V PS12650 NP65 12 BS13...

Страница 3: ...N Fault Condition Possible Cause Action CLOSED CLOSED Normal operation Mains present Battery healthy None OPEN CLOSED Standby Mode Mains lost Battery driving load Investigate loss of mains CLOSED OPEN...

Страница 4: ...e monitor disconnected or damaged PSU running in Safe Mode Check temperature sensor connections and condition of sensor Replace if suspect ON CONTINUOUS ON or OFF Internal Fault Software fault detecte...

Страница 5: ...signed to support two 17 or 18 Ah batteries and as such weighs a total of 19 5 Kg when loaded Ensure that wall fixings are appropriate to support this weight 6 The product should be mounted no further...

Страница 6: ...ed by conduit if it is being used to power the CIE directly 16 Fix to wall or other structure in correct orientation i e with hinge on left hand side using screws of sufficient size and length through...

Страница 7: ...ling 4 Connect the EPS and PSU Fault outputs to the appropriate inputs of control equipment if remote fault monitoring is required Figure 4 Power Load and Battery connections 5 Connect the load output...

Страница 8: ...4 5 14 Connect the battery temperature sensor two white wires to the PCB terminals TMP Sens See Figure 5 15 If the batteries are housed remotely replace the battery lead assembly including battery te...

Страница 9: ...arts inside There is no regular maintenance required of the PSU other than periodic testing and replacement of the standby battery Reference should be made to the battery manufacturer s documentation...

Страница 10: ...sposal route in accordance with all national and local regulations Before disposal of the product any batteries must be removed and disposed separately via an appropriate approved battery disposal rou...

Отзывы: