S

PECIFICATION

 

 

 

Mains Input 

Rated Voltage 

110 – 240V ac  

Frequency 

50 Hz 

Input current 

< 4.0 Amps at full load 

Inrush current 

30 A Max at 25 °C 110V ac for 10 ms 

Fuse 

T4.0 A, 20 mm, 250V ac HRC 

 
Output 

Voltage at full load 

 

Mains power 

 

Battery standby 

 
 

26.0 – 28.5 Vdc  (range) (27.6 V nominal) 

 

18 – 26.0 Vdc  

Ripple 

<100 mV pk – pk max @ Rated Voltage 

 

Fuse 
 

Load 

 

Battery 

 

F10.0 A 
F10.0 A 

Overload 

Electronic shutdown at 15 A until overload or short circuit removed

 

Battery mode selected 

17/18 Ah 

 

38 Ah

 

65 Ah

 

Continuous Output Current 

No charging (Imax B)  

With charging  (Imax A) – 220V 

With charging (Imax A) – 110V 

 

10.0 A 
10.0 A 

8.5 A 

 

10.0 A 

8.0 A 
7.5 A 

 

10.0 A 

7.2 A 
6.5 A 

Battery Capacity 
eg 

-

 

PowerSonic model 

-

 

Yuasa model 

-

 

Interlogix model

 

2 x 17/18Ah 12 V 

 

PS12170 
NP17-12 

BS131N 

2 x 38 Ah 12 V 

 

PS12380 
NP38-12 

 

2 x 65 Ah 12 V 

 

PS12650 
NP65-12 

BS133N 

Battery Charging 

Constant current bulk charging to 80% capacity within 24 hours 
Float charging to 100% within 48 hours 
Eco charging and check every 2 hours – (for 20 minutes) 

Constant current charge 

0.7 A 

1.6 A 

2.6 A 

Low battery threshold voltage 

23 V 

Deep discharge protection 

Threshold voltage – 21 V 

Quiescent current – no load 

30 mA 

Quiescent current – batt cut off 

0 mA 

 

 

Mechanical 

Product Reference 

STX2410-E 

STX2410-H 

BATT-BOX-65 

Enclosure Dimensions 

 w x h x d (mm) 

400 x 420 x 80 

420 x 420 x 180 

450 x 535 x 245 

Weight (kg)

 excluding battery 

6.4 

9.7 

12.9 

Material  

1.2mm steel white powder coated 

 

Environmental  

Temperature – Operating 

-10 to +40°C (operating) 75% RH non-condensing 

Temperature - Storage 

-20 to +80°C (storage) 

 

Содержание BATT-BOX-65

Страница 1: ...volt free solid state relay fault output signal i loss of mains and ii battery fault charger fault and loss of output In addition there is an RS232 serial interface that can provide diagnostic and fau...

Страница 2: ...A 7 5 A 10 0 A 7 2 A 6 5 A Battery Capacity eg PowerSonic model Yuasa model Interlogix model 2 x 17 18Ah 12 V PS12170 NP17 12 BS131N 2 x 38 Ah 12 V PS12380 NP38 12 2 x 65 Ah 12 V PS12650 NP65 12 BS13...

Страница 3: ...N Fault Condition Possible Cause Action CLOSED CLOSED Normal operation Mains present Battery healthy None OPEN CLOSED Standby Mode Mains lost Battery driving load Investigate loss of mains CLOSED OPEN...

Страница 4: ...e monitor disconnected or damaged PSU running in Safe Mode Check temperature sensor connections and condition of sensor Replace if suspect ON CONTINUOUS ON or OFF Internal Fault Software fault detecte...

Страница 5: ...signed to support two 17 or 18 Ah batteries and as such weighs a total of 19 5 Kg when loaded Ensure that wall fixings are appropriate to support this weight 6 The product should be mounted no further...

Страница 6: ...ed by conduit if it is being used to power the CIE directly 16 Fix to wall or other structure in correct orientation i e with hinge on left hand side using screws of sufficient size and length through...

Страница 7: ...ling 4 Connect the EPS and PSU Fault outputs to the appropriate inputs of control equipment if remote fault monitoring is required Figure 4 Power Load and Battery connections 5 Connect the load output...

Страница 8: ...4 5 14 Connect the battery temperature sensor two white wires to the PCB terminals TMP Sens See Figure 5 15 If the batteries are housed remotely replace the battery lead assembly including battery te...

Страница 9: ...arts inside There is no regular maintenance required of the PSU other than periodic testing and replacement of the standby battery Reference should be made to the battery manufacturer s documentation...

Страница 10: ...sposal route in accordance with all national and local regulations Before disposal of the product any batteries must be removed and disposed separately via an appropriate approved battery disposal rou...

Отзывы: