OMMISSIONING
Mains Power Up
1)
With no external connections made to the PSU, connect the mains input wires to the terminal block,
ensuring that the mains isolator (disconnect device) is open
. Fasten wiring in place with cable tie to
saddle.
Note: Equipment must be earthed.
2)
Apply mains input. Ensure that the green Mains LED illuminates and that the yellow Fault LED flashes after
approximately 20s (indicating a disconnected battery).
3)
Disconnect the mains power.
Load Output and Remote Signalling
4)
Connect the EPS and PSU Fault outputs to the appropriate inputs of control equipment if remote fault
monitoring is required.
Figure 4 – Power, Load and Battery connections
5)
Connect the load (output) wiring as shown in Figure 4. Cable tie to saddle provided (adjacent to exit hole).
6)
Re-apply mains. Verify that the green Mains LED illuminates and the yellow Fault LED flashes after
approximately 20 s (disconnected battery).
7)
If connected, verify that the EPS Fault monitor shows a
closed
contact and the PSU Fault monitor shows an
open
contact.
8)
Perform a full functional test of system including full alarm condition
.
9)
Disconnect the mains supply.
Figure 5 – Terminal labels
+
+
+
-
To Load
L E N
n/c |GEN| EPS|TMP|+ - | + + - -
| FAULT |Sens|Bat| O/P
L E N
AC in
BATTERY | DIAG| OUTPUT LOAD
FUSE | LED| FUSE
Main input
Fuse