background image

10 

 

 

Technical Support: +44(0)23 9269 6638 (option 3) 

  PAK200574_01K May  2016                       ©2016 ELMDENE INTERNATIONAL LTD  

 

C

OMPLIANCE

 

 

 

This power supply unit meets the essential requirements of the following EU Directives: 

CPR: 305/2011 EU 

EMC: 2014/30/EU 

Low Voltage: 2014/35/EU 

WEEE: 2012/19/EU 

RoHS2: 2011/65/EU 

 
 

 

 

 

 

 
 

 

 
 

 

 
 

 

 

 

Functional standard:   

EN54-4:1997 +A1 +A2 
Environmental Class II  

Certification Body: 

 

Underwriters Laboratory 

 

 

 
Declaration of Performance 

DOP2014/08 

  

 

DOP2014/09 

 

 

 

D

ISPOSAL OF 

P

RODUCT AT 

E

ND OF 

L

IFE

 

 

 
This product falls within the scope of EU Directives 2012/19/EU Waste Electrical and Electronic Equipment 
(WEEE)  and  2013/56/EU  (Battery).  At  the  end  of  life,  the  product  must  be  separated  from  the  domestic 
waste stream and disposed via an appropriate approved WEEE disposal route in accordance with all national 
and local regulations. 
Before disposal of the product, any batteries must be removed, and disposed separately via an appropriate 
approved battery disposal route in accordance with all national and local regulations. Package used batteries 
safely for onward transport to your supplier, collection point or disposal facility. 
 

Caution:  Risk of fire or explosion  

if bare battery wires are allowed to touch. 

 
See  Specification  for  battery  type  information.  The  battery  is  marked  with  the  crossed  out  wheelie  bin 
symbol, which may include lettering to indicate cadmium (Cd), lead (Pb), or mercury (Hg). 
 

For more information see: 

www.recyclethis.info

 

 
 
 
 
 
 
 
 
 
 
 
 
 

The packaging supplied with this product may be recycled. 

 Please dispose of packaging accordingly. 

 

0843 

 

Elmdene International Ltd 3 Keel 

Close Portsmouth PO35QD 

14 

0843-CPR-0216 

EN54-4:1A1 +A2 

Power Supplies intended for use in 

fire detection and fire alarm 

systems 

Содержание BATT-BOX-65

Страница 1: ...volt free solid state relay fault output signal i loss of mains and ii battery fault charger fault and loss of output In addition there is an RS232 serial interface that can provide diagnostic and fau...

Страница 2: ...A 7 5 A 10 0 A 7 2 A 6 5 A Battery Capacity eg PowerSonic model Yuasa model Interlogix model 2 x 17 18Ah 12 V PS12170 NP17 12 BS131N 2 x 38 Ah 12 V PS12380 NP38 12 2 x 65 Ah 12 V PS12650 NP65 12 BS13...

Страница 3: ...N Fault Condition Possible Cause Action CLOSED CLOSED Normal operation Mains present Battery healthy None OPEN CLOSED Standby Mode Mains lost Battery driving load Investigate loss of mains CLOSED OPEN...

Страница 4: ...e monitor disconnected or damaged PSU running in Safe Mode Check temperature sensor connections and condition of sensor Replace if suspect ON CONTINUOUS ON or OFF Internal Fault Software fault detecte...

Страница 5: ...signed to support two 17 or 18 Ah batteries and as such weighs a total of 19 5 Kg when loaded Ensure that wall fixings are appropriate to support this weight 6 The product should be mounted no further...

Страница 6: ...ed by conduit if it is being used to power the CIE directly 16 Fix to wall or other structure in correct orientation i e with hinge on left hand side using screws of sufficient size and length through...

Страница 7: ...ling 4 Connect the EPS and PSU Fault outputs to the appropriate inputs of control equipment if remote fault monitoring is required Figure 4 Power Load and Battery connections 5 Connect the load output...

Страница 8: ...4 5 14 Connect the battery temperature sensor two white wires to the PCB terminals TMP Sens See Figure 5 15 If the batteries are housed remotely replace the battery lead assembly including battery te...

Страница 9: ...arts inside There is no regular maintenance required of the PSU other than periodic testing and replacement of the standby battery Reference should be made to the battery manufacturer s documentation...

Страница 10: ...sposal route in accordance with all national and local regulations Before disposal of the product any batteries must be removed and disposed separately via an appropriate approved battery disposal rou...