Where the PSU Fault and EPS Fault outputs are used, they should only be connected to circuits having voltages less
than 60 Vdc.
Cable Sizing
1)
Mains input cable must be to the applicable standard with a 5 A or greater current capacity, i.e. 0.75 mm
2
nominal conductor area, having a minimum operating voltage of 300/500 Vac.
2)
The low voltage output cable must be sized to carry the rated load current to the devices connected to the
PSU.
3)
Mains input and low voltage output cables should be routed to use different entry / exit holes in the case.
Bushes should be used to protect cable sheaths from chafing. Ensure that these bushes are correctly sized
(i.e. close fitting with respect to cable sizing). Note that the bushes should meet a minimum flammability
specification of UL94 HB.
4)
All cabling should be securely fastened in position using a cable tie through the saddles provided.
Mounting – E box – 17 or 18 Ah
5)
The E box is designed to support two 17 or 18 Ah batteries and as such weighs a total of 19.5 Kg when
loaded. Ensure that wall fixings are appropriate to support this weight.
6)
The product should be mounted no further than 10 cm from the control and indicating equipment, close
coupled by conduit if it is being used to power the CIE directly.
7)
Fix to wall or other support structure in correct orientation i.e. with hinge on left hand side, using screws
of sufficient size and length through the mounting holes.
8)
Protect the battery terminals from any metal surfaces during installation as shorting of the terminals is
extremely hazardous.
9)
Knock-outs are provided in the case for mating with external trunking or conduit.
10)
Ensure that all unused holes (on the rear of the case) are sealed to prevent the ingress of damp and dust.
Figure 1 – E Box and Battery mounting
Mounting – BATT- BOX – 65 Ah
11)
The Battery box is used for 65 Ah batteries is designed to be floor mounted. DO NOT suspend from a wall.
12)
It is important that the battery box and the PSU are co-located as shown, and connected using the
provided extended 3 metre cable.
13)
A fixing bracket is provided to secure the Battery Box to the wall to prevent it moving away from the wall.