ID 983-985 LX (/C /CK) HACCP
7/12
PAR.
Fot
FAd
Fdt
dt
dFd
FCO
Fod
FdC
Fon
FoF
Att
AFd
HAL (5)
LAL (5)
PAO (!)
(8)
dAO
OAO
tdO
tAO (8)
dAt
EAL
AOP
PbA
SA3
dA3
dSd
dLt
OFL
dOd
dAd
L00
L01
L02
L03
L04
L05
D
DE
ES
SC
CR
RIIP
PT
TIIO
ON
N
Fan on-start temperature. Fan start temperature; if the temperature read by the evapora-
tor is lower than the value set for this parameter, the fans remain deactivated. The value
is positive or negative and, depending on the FPt parameter, could represent the temper-
ature in absolute value or relative to Set point.
FAn differential. Fan activation intervention differential (see par. “FSt” and “Fot”).
Fan delay time. Delay time between start-up of fan after defrosting.
drainage time. Dripping time.
defrost Fan disable. Used to select exclusion of evaporator fans during defrosting.
y = yes; n = no.
Fan Compressor OFF. Used to select fan stop when compressor is switched OFF.
y = fans active (with thermostat; in response to the value read by the defrost probe, see
“FSt” parameter);
n = fans off;
dc = duty cycle (using parameters “Fon” and “FoF”).
Fan open door open. Used to select the fan stop when door is open and fan re-start
when door is closed (if they were active). n=fans stop; y=fans unchanged.
Fan delay Compressor off. Fan switch off delay time after compressor stop. In minutes.
0= function excluded
Fan on (in duty cycle).
Time fans are ON in duty cycle. Use of fans in duty cycle mode; valid for FCO = dc and
H42=1 (probe 2 present) (evaporator))
Fan OFF (in duty cycle).
Time fans are OFF in duty cycle. Use of fans in duty cycle mode; valid for FCO = dc and
H42=1 (probe 2 present) (evaporator))
ALARMS (folder with “AL” label)
Alarm type. Parameter “HAL” and “LAL” modes, as absolute temperature values or as dif-
ferential compared to the Set point.
0 = absolute value; 1 = relative value.
Alarm diFferential. Alarm differential.
Higher ALarm. Maximum alarm. Temperature value (considered as distance from Set
point or as an absolute value based on Att) which if gone above triggers the alarm signal.
See Max/Min. Alarm Diagram;
Lower ALarm. Minimum alarm. Temperature value (considered as distance from Set point
or as an absolute value based on Att) which if gone below triggers the alarm signal.
See Max/Min. Alarm Diagram;
Power-on Alarm Override. Alarm exclusion time after instrument start-up, after a power
failure.
defrost Alarm Override. Alarm exclusion time after defrost.
(*)To prevent false HACCP alarms after a defrost cycle, signalling is inhibited for a period
of time set by this parameter
Alarm signal delay after disabling digital input (door open). Alarm refers to a high and
low temperature alarm.
time out door Open. Time out after alarm signal following digital input disabling (door
open).
temperature Alarm Override. Temperature alarm signal delay time.
defrost Alarm time. Alarm signal for defrost end due to time-out.
n = does not activate alarm; y = activates alarm.
External Alarm Lock. External alarm to lock controllers (n=does not lock, y=locks).
Alarm Output Polarity. Polarity of alarm output.
0 = alarm active and output disabled;
1 = alarm active and output enabled.
Configuration of temperature alarm on probe 1 and/or 3.
0 = alarm on probe 1 (thermostat control);
1 = alarm on probe 3 (display);
2 = alarm on probe 1 and 3 (thermostat control and display).
3 = alarm on probe 1and 3 (thermostat control and display) on external threshold
Probe 3 alarm set point (display)
Probe 3 alarm differential (display)
LIGHT AND DIGITAL INPUTS (folder with “Lit” label)
Light relay enable from door switch.
n = door open, light does not turn on;
y = door open, light turns on (if it was off).
Light relay disabling (switch off) delay (cell light). The cell light will remain on for dLt
minutes after closing the door if the dSd parameter is set to do this.
Light switch always disables light relay. Enables switching off with light button even if the
delay after closing the door set by dLt is active.
Door switch switches off loads. When commanded by the digital input, programmed as
door-switch, it stops all the loads when the door is opened and re-starts them when the
door is closed (observing any timings in progress).
Digital input activation delay
(FOR /CK MODELS ONLY) LINK CONTROLLER(folder with “Lin” label)
Selects the instrument as Master (0), Slave (from 1 to 7), Echo (0, in this case the Echo
serves as a repeater for the Master even if connected to a Slave).
Refers to Master only. Number of Slaves in network (from 0 to 7). Per Slaves/Echoes leave
value =0
Presence of local Echoes referring to single Slave. 0 = Local echo not present; 1 = Echo
present and shares the Slave display at a set rate; if Master or Slave, it determines if the
device is active and shares its local display at a set rate. 2 = the Echo shows the display
of the associated Slave (Slave and associated Echo must have the same address L00). If it
is directly connected to the Master, it displays the Master display.
Refers to Master and Slave. Simultaneous/sequential defrosting. Master: n = simultaneous;
y = sequential. Slave: n = ignore; y = accept.
Refers to Slave only. Distributed display. n = the Slave displays local values; y = the Slave
displays Master display
Refers to Master and Slave. Master: n = does not ask Slaves to activate remote functions;
y = asks Slaves to activate remote functions. Slave: n = ignores activation of remote func-
tions from Master; y = accepts activation of remote functions from Master.
DEFAULT
-18.0
2.0
0
0
y
y
n
0
0
0
0
2.0
50.0
-50.0
0
120min
0
0
0
n
n
1
0
0
2.0
y
0
n
n
0
0
0
0
n
y
n
RANGE
-50.0..150.0
1.0…50.0
0...250
0...250
n/y
n/y/dc
n/y
0..99
0..99
0..99
0/1
1.0...50.0
LAL...150.0
-50.0...HAL
0...10
0..999
0…10
0...250
0...250
n/y
n/y
0/1
0…3
-50.0…150.0
-30.0…30.0
n/y
0…31
n/y
n/y
0…255
0...7
0...7
0/1/2
n/y
n/y
n/y
VALUE*
LEVEL**
2
1
1
1
1
1
2
2
2
2
2
1
1
1
1
1
2
2
1
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
U.M.
°C/°F
°C/°F
min
min
flag
num
flag
min
min
min
flag
°C/°F
°C/°F
°C/°F
hours
min
hours
min
min
flag
flag
flag
min
°C/°F
°C/°F
flag
min
flag
flag
min
num
num
num
flag
flag
flag