![Electro Industries/GaugeTech Shark 100B Скачать руководство пользователя страница 95](http://html.mh-extra.com/html/electro-industries-gaugetech/shark-100b/shark-100b_installation-and-operation-manual_2379723095.webp)
Doc
#
E145701
5-13
5: Communication Installation
Electro
Industries/GaugeTech
™
Powered by Innovation™
5. Change ONLY the parameters in group 1. To do so:
a. Type number "
1
."
b. Once group 1 is selected, the individual parameters display for editing. Either:
• Enter a new parameter if a change is required.
• Press
Enter
to proceed to the next parameter without changing the
current setting.
IMPORTANT!
Settings 2, 3, and 4 must have the default values shown above.
(
Example
: Setting device with static IP Address.)
IP Address <010> 192.<000> 168.<000> .<000> .<001>
Set Gateway IP Address <N>? Y
Gateway IP Address: <192> .<168> .<000> .<001>
Set Netmask <N for default> <Y>? Y
1) Network/IP Settings:
IP Address ...............….. 10.0.0.1
Default Gateway .............--- not set ---
Netmask .....................…255.255.255.0
2) Serial & Mode Settings:
Protocol ...................... Modbus/RTU,Slave(s) attached
Serial Interface ........... 57600,8,N,1,RS232,CH1
3) Modem/Configurable Pin Settings:
CP1…………..Not Used
CP2…………..Not Used
CP3…………..Not Used
4) Advanced Modbus Protocol settings:
Slave Addr/Unit Id Source .. Modbus/TCP header
Modbus Serial Broadcasts ... Disabled (Id=0 auto-mapped to 1)
MB/TCP Exception Codes ..... Yes (return 00AH and 00BH)
Char, Message Timeout ...... 00050msec, 05000msec
D)efault settings, S)ave, Q)uit without save
Select Command or parameter set (1..4) to change: