6: Using the Shark® 100 Meter
Electro
Industries/GaugeTech
™
Powered by Innovation™
6.2.5.4: Configuring Connection Setting
1. Press the
Enter
button when Cnct is in the A window. The Cnct screen appears.
2. Press the
Right
button or
Down
button to select a configuration. The choices are:
• 3 Element Wye (3 EL WYE)
• 2.5 Element Wye (2.5EL WYE)
• 2 CT Delta (2 Ct dEL)
NOTE:
If you are prompted to enter a password, refer to Section 6.2.4 for instruc-
tions on doing so.
3. When you have made your selection, press the
Menu
button twice.
4. The STOR ALL YES screen appears. Press
Enter
to save the setting.
Use buttons to select configuration
6.2.5.5: Configuring Communication Port Setting
Port configuration consists of: Address (a three digit number), Baud Rate (9600;
19200; 38400; or 57600), and Protocol (DNP 3.0; Modbus RTU; or Modbus ASCII).
1. Press the
Enter
button when POrt is in the A window. The Adr (address) screen
appears. You can either:
• Enter the address.
• Access one of the other Port screens by pressing the
Enter
button: press
Enter
once to access the bAUd screen (Baud Rate), twice to access the Prot screen
(Protocol).
A
B
C
-
-
-
MENU
ENTER