D: DNP 3.0 Protocol Assignments
Electro
Industries/GaugeTech
™
Powered by Innovation™
D.4.1.3: 32-Bit Binary Counter Without Flag (Obj. 20, Var. 5)
Counters support the following functions:
Read (Function 1)
A READ request for Variation 0 is responded to with Variation 5.
Counters are used to communicate the following data measured by Shark® 100
meters:
Hour Readings
Hour Readings (Points 0 - 4)
NOTE:
These readings may be cleared by using the Control Relay Output Block (see
previous Section D.4.1.2).
D.4.1.4: 16-Bit Analog Input Without Flag (Obj. 30, Var. 4)
Analog Inputs support the following functions:
Read (Function 1)
A READ request for Variation 0 is responded to with Variation 4.
Analog Inputs are used to communicate the following data measured by Shark® 100
meters:
• Health Check
• Phase-to-Neutral Voltage
• Phase-to-Phase Voltage
Point
Readings
Unit
0
+W hour
Wh
1
-W hour
Wh
2
+VAR hour
VARh
3
-VAR hour
VARh
4
+VA hour
VAh