Doc# E151701 4-4
4: Performing Meter Testing
Electro
Industries/GaugeTech
™
Powered by Innovation™
4.2.1: Entering Test Mode
To enter Test Mode, you must bypass the meter’s security system. In most instances,
this requires you to remove power from the meter, break the meter seal and remove
the Lexan cover, and then re-power the meter. If the meter is in a switchboard case,
you’ll first need to remove it from the case - see 6.2.1: Removing the Meter from the
Switchboard Case/Reinstalling the Meter into the Switchboard Case on page 6-14.
4.2.2: Using Test Mode
The same selected measurement profile quantities (data accumulations) that are
calculated during normal operation are calculated in Test Mode. Display quantities
(Watt-hour, VAR-hour, Volt-Ampere-hour and Block Demand quantities) are displayed
in units rather than kilo-units; i.e. the data is displayed as Wh, VARh, VAh and watts
rather than kWh, kVARh, kVAh and kW. The same Demand values calculated during
normal operation are also calculated in Test Mode. The display formats in Test Mode
are changed to provide greater resolution during test operations.
The display does not scroll while in Test Mode. Each item remains displayed until the
Test Button is pressed, which causes the next Test Mode screen to display.
The following table shows the display screens available in Test Mode, the data
displayed on each screen and the pulse source for each screen.
Table 1:
Test Mode Displayed Data and Pulse Source
Test Mode
Displayed Data
Pulse Source
Wh - Del
Delivered Wh Energy
kWh, Del
Wh - Rec
Received Wh Energy
kWh, Rec
VARh - Q1 and Q2
VARh in Quadrant1
VARh in Quadrant 2
kVARhr, Del
VARh - Q 3 and Q4
VARh in Quadrant 3
VARh in Quadrant 4
kVARhr, Rec
VAh - Q1 and Q4
VAh in Quadrant 1
VAh in Quadrant 4
kVAhr, Q1
VAh - Q2 and Q3
VAh in Quadrant 2
VAh in Quadrant 3
kVAhr, Q3
Watt Demand Rolling
Watt Rolling Demand
Delivered
kWH, Del
Содержание Nexus 1262
Страница 1: ......
Страница 2: ...This page intentionally left blank ...
Страница 4: ...Doc E151701 ii Electro Industries GaugeTech Powered by Innovation This page intentionally left blank ...
Страница 86: ... RF 2SHUDWLQJ QVWUXFWLRQV 7KLV SDJH LQWHQWLRQDOO OHIW EODQN ...
Страница 97: ...This page intentionally left blank ...
Страница 98: ......
Страница 272: ...Doc E151701 A 2 A TLC Spreadsheet and Examples Electro Industries GaugeTech Powered by Innovation ...
Страница 273: ...Doc E151701 A 3 A TLC Spreadsheet and Examples Electro Industries GaugeTech Powered by Innovation ...
Страница 274: ...Doc E151701 A 4 A TLC Spreadsheet and Examples Electro Industries GaugeTech Powered by Innovation ...
Страница 275: ...Doc E151701 A 5 A TLC Spreadsheet and Examples Electro Industries GaugeTech Powered by Innovation ...