![Electro Industries/GaugeTech Nexus 1262 Скачать руководство пользователя страница 175](http://html.mh-extra.com/html/electro-industries-gaugetech/nexus-1262/nexus-1262_user-manual_2379732175.webp)
Doc# E151701 9-5
9: External I/O Modules
Electro
Industries/GaugeTech
™
Powered by Innovation™
9.3.1: Steps for Attaching Multiple I/O Modules
1. Each I/O module in a group must be assigned a unique address. See the
CommunicatorPQA®, MeterManagerPQA
®
, and EnergyPQA.com
®
Software User
Manual
for details on configuring and programming the I/O Modules.
2. Determine how many power sources (such as the PSIO) are needed for the number
of modules in use. See Sections 5.3.9 for details.
3. I/O modules can be mounted using either of two methods. The first method is
using the mounting brackets provided, to attach directly to a panel. The second
method is to attach the Din Rail clips to the mounting brackets to connect the I/O
modules to a DIN rail mounting system.
4. Starting with the left module and using a slotted screwdriver, fasten the first I/O
module to the left mounting bracket of the MBIO mounting brackets kit. The left
mounting bracket is the one with the PEM. Fasten the internal screw tightly into the
left mounting bracket.
5. Slide the female RS485 port into the male RS485 side port to connect the next
I/O module to the left module. Fasten together enough to grab but do not tighten,
yet.
6. Combine the modules together, one by one.
7. Attach the PSIO (power supply) to the right of the group of I/O Modules it is
supplying with power.
NOTE:
The PB1 can also be used as a Low Voltage Power Supply. It must be mounted
separately. The PB1 should be ordered with a 12 V output for this application.
8. Once you have combined all the I/O modules and power supplies together for the
group, fasten tightly. This final tightening will lock the whole group together as a
unit.
9. Attach the right Mounting Bracket to the right side of the group using the small
Phillips head screws provided.
Содержание Nexus 1262
Страница 1: ......
Страница 2: ...This page intentionally left blank ...
Страница 4: ...Doc E151701 ii Electro Industries GaugeTech Powered by Innovation This page intentionally left blank ...
Страница 86: ... RF 2SHUDWLQJ QVWUXFWLRQV 7KLV SDJH LQWHQWLRQDOO OHIW EODQN ...
Страница 97: ...This page intentionally left blank ...
Страница 98: ......
Страница 272: ...Doc E151701 A 2 A TLC Spreadsheet and Examples Electro Industries GaugeTech Powered by Innovation ...
Страница 273: ...Doc E151701 A 3 A TLC Spreadsheet and Examples Electro Industries GaugeTech Powered by Innovation ...
Страница 274: ...Doc E151701 A 4 A TLC Spreadsheet and Examples Electro Industries GaugeTech Powered by Innovation ...
Страница 275: ...Doc E151701 A 5 A TLC Spreadsheet and Examples Electro Industries GaugeTech Powered by Innovation ...