8: Transformer Loss Compensation
Electro
Industries/GaugeTech
™
Powered by Innovation™
Calculate Load Loss Values
Enter "Value at Meter Base" from Normalize Losses section. Enter "Meter Base kVA"
from previous calculation. Calculate "% Loss at Meter Base" by dividing (Value at
Meter Base) by (Meter Base kVA) and multiplying by 100.
Enter calculated % Loss Watts values into the Nexus® meter using Communica-
torPQA® software. Refer to Appendix B of the
CommunicatorPQA
®
, MeterManager-
PQA
®
, and EnergyPQA.com
®
Software User Manual
for instructions.
Table 11:
Quantity
Value at
Meter Base
Meter Base
kVA
% Loss at
Meter Base
Quantity
No-Load
Loss kW
% Loss
Watts FE
No-Load
Loss kVAR
% Loss
VARs FE
Load Loss
kW
% Loss
Watts CU
Load Loss
kVAR
% Loss
VARs CU
Содержание Nexus 1262
Страница 1: ......
Страница 2: ...This page intentionally left blank ...
Страница 4: ...Doc E151701 ii Electro Industries GaugeTech Powered by Innovation This page intentionally left blank ...
Страница 86: ... RF 2SHUDWLQJ QVWUXFWLRQV 7KLV SDJH LQWHQWLRQDOO OHIW EODQN ...
Страница 97: ...This page intentionally left blank ...
Страница 98: ......
Страница 272: ...Doc E151701 A 2 A TLC Spreadsheet and Examples Electro Industries GaugeTech Powered by Innovation ...
Страница 273: ...Doc E151701 A 3 A TLC Spreadsheet and Examples Electro Industries GaugeTech Powered by Innovation ...
Страница 274: ...Doc E151701 A 4 A TLC Spreadsheet and Examples Electro Industries GaugeTech Powered by Innovation ...
Страница 275: ...Doc E151701 A 5 A TLC Spreadsheet and Examples Electro Industries GaugeTech Powered by Innovation ...