background image

 

 

EDA-Z1000 - Installation and Operation Manual                                                                                                                  

 
 

1. Introduction 

 
Electro Detectors has been manufacturing radio fire alarm systems for over 16 years and has now complemented its range of 
products with a smaller purpose built control panel , the Zerio system. It has been designed for smaller systems and is capable of 
handling 99 devices in 8 zones. Typical installations could be small offices, private houses, HMO’s, guest houses and small hotels. 
 
The system has been designed to allow very simple set up with most operations being automated. 
 
The system is capable of displaying full text and having sophisticated cause and effect programming. 
 
The panel requires a single 2.8Ahr Lead Acid battery to achieve 48 hours standby.  Two 6V 4Ahr batteries connected in series will 
provide a 72- hour HMO compliant standby. 
 
Devices for the system are visually the same as the standard Millennium devices but are labelled differently with a yellow label. In 
order to maintain compatibility, the Zerio panel can re-program a Millennium device to operate with the Zerio format, providing the 
devices are version V1.6 or later. 
 
A memory module is plugged into the processor board. This stores a copy of any set-up information including device text and cause 
and effects. This can be used as a means of swapping data between panels should the need arise.  
 
In order to log devices and program devices into the system, they need to be connected via a supplied programming lead. The 
system also stores the data programmed into each device allowing replacement devices to be easily cloned onto the system.  
 
Prior to installation, the building where the system is to be installed must be surveyed to ensure that each device to be fitted has a 
good radio communication path to the control panel. If this is not done correctly the system will operate unreliably.  
Having successfully completed this survey, when installing the devices, they must be positioned as per the survey. Installing a 
device only a few tens of centimetres away from the surveyed position can reduce the signal strength significantly, especially if any 
metal work is contained in the ceiling above the new position (e.g. air-conditioning ducting). 
 
When manufactured each device is programmed with a unique ID. Whenever a device transmits a message this ID is included as part 
of the message. Also included in the message is the status (i.e. alarm condition, unit removal, low battery etc). The amount of smoke 
inside the head at the time of the transmission is included as part of the message. Even if there is no change in status, the device will 
transmit an ‘I’m OK’ verify message approximately every 3 minutes. If these transmissions are not received from the device within 
the verify period (typically 120 minutes) then a ‘Verify Fail’ fault is generated. 
 

    

Version Z1000/V1.05 

 

Electro-Detectors                      

Page 

5

 

   

Содержание EDA-Z1000

Страница 1: ...tem Operation Manual Electro Detectors Ltd Electro House Edinburgh Way Harlow Essex CM20 2EG UK Tel 01279 635668 Fax 01279 450185 Email eda electrodetectors co uk Web www electrodetectors co uk Electro Detectors Version Z1000 V1 05 ...

Страница 2: ...viceable parts are contained within this panel Always refer to a qualified technician for parts and servicing This manual should be provided to the site s nominated responsible person and left on the premises for easy reference Version Z1000 V1 05 Electro Detectors Page 2 ...

Страница 3: ...na monitoring configuration added V1 02 DR 0 10 22 12 05 Must reset booster panel to ensure memory cleared All other devices should also be reset on power up Operation of fire relays when silence reset pressed V1 03 SM 0 15 13 06 06 New features for disabling faults and Double knock functions V1 04 SM 1 01 14 03 07 New menu structure Survey mode function keys and sounder circuit V1 05 SM 1 02 18 0...

Страница 4: ...To Silence Sounders 3 7 To Re sound the Sounders 3 8 To Reset an Alarm 3 9 Menu Navigation 3 10 To Change Date and Time 3 11 To Isolate a Zone 3 12 To Isolate a Device 3 13 To Enable a Zone 3 14 To Enable a Device 3 15 View System History of Events 4 0 Advanced User Operations 4 1 General 4 2 To View Access Codes 4 3 Changing Access Codes 4 4 To Select a Test Mode 4 5 To Disable a Test Mode Versio...

Страница 5: ...uld the need arise In order to log devices and program devices into the system they need to be connected via a supplied programming lead The system also stores the data programmed into each device allowing replacement devices to be easily cloned onto the system Prior to installation the building where the system is to be installed must be surveyed to ensure that each device to be fitted has a good...

Страница 6: ...n the up and down arrow keys allow the user to scroll through all the current events The display will also scroll automatically every 6 seconds Keys Function 1 2 Programmable for use as Evacuate and Alert functions Cancel Used to return to the main screen from a menu or to return to the menu from a programming screen Enter This is used to accept information programmed into the panel Menu Press to ...

Страница 7: ...er Once the Silence buzzer button has been pressed the panel assumes that the fault has been acknowledged and does not resound the buzzer If a different fault occurs the panel will sound the buzzer until the new fault has been acknowledged 3 4 To Reset a Fault Assuming the fault has been rectified pressing reset will reset the system and the system normal screen will be displayed If the fault is s...

Страница 8: ...that occurred during the alarm condition 3 9 Menu Navigation To enter the menu system press MENU and enter a valid password Main Menu will appear To scroll through the menu the or keys should be pressed In order to select a menu option the key should be pressed To return to the previous menu screen from a sub menu the should be pressed Pressing Cancel will return to the system screen where any fau...

Страница 9: ...ther Disablement conditions such as isolated devices exist Select Zone 01 Press ENTER to enable Zone 01 ENTER to continue 3 14 To Enable a Device To enable a previously isolated device press MENU and enter a valid password Select 2 Disable Enable select 2 Enable select 2 Enable Device Using the or keys select the device number to be enabled and press ENTER To enable more devices press ENTER or CAN...

Страница 10: ...n re enter the new password to confirm Press ENTER to save the new password A message will be displayed indicating that the password is being saved to the SIM and flash memory Access Level 1 Enter Current Code Enter New Code Confirm New Code Basic User ENTER to continue Hold CANCEL to exit Hold CANCEL to exit Hold CANCEL to exit 4 3 To Select Test Mode Test mode is available to an advanced user so...

Страница 11: ... It can be set in 1 hour intervals and is selected using the cursor keys A maximum of 48 hours can be set The user should now press enter to enable the test mode The Test Mode LED will illuminate Test Mode Enabled Save Test Settings YES ENTER to Continue Once test options have been selected these can now be saved for quick setup in the future Once the test screen is entered the panel will prompt t...

Страница 12: ...EDA Z1000 Installation and Operation Manual Version Z1000 V1 05 Electro Detectors Page 12 ...

Отзывы: