background image

 

PRODUCT MAINTENANCE 

 

 

NP-DK50-Nx2VTM-AD-EN-6_04-2022 

44 

04/2022 

18.2.  Check of product operation 

  Check  air  pump  condition 

–  the 

aggregates 

should 

be 

operating 

normally without excessive vibration or 
noise.  Troubleshoot  any  problem  or 
call  in  service  personnel  if  trouble  is 
detected. 

  Visually  inspect  fan  operation 

–  the 

fans  must  be  operating  when  the 
aggregates are running. Troubleshoot 
any  problem  or  call  in  service 
personnel if trouble is detected. 

  Check  to  ensure  the  power  cord,  the 

cable  for  the  pressure  sensor  on  the 
air 

tank 

and 

the 

connecting 

compressed 

air 

hoses 

are 

undamaged. 

Replace 

damaged 

components 

or 

call 

in 

service 

personnel. 

  Check the ambient temperature at the 

display 

–  the  ambient  temperature 

must  be  below  the  temperature  limit 
(40°C).  Cool  the  space  if  the 
temperature is high. 

  Check  for  alarm  conditions  on  the 

display 

– troubleshoot and remedy all 

alarms. 

18.3.  Check the compressed air 

connections for leaks and inspect 
the equipment 

Leak testing 

  Check  the  compressor's  compressed 

air  lines  for  leaks  during  operation 

– 

pressure supplied by the compressor. 

  Use a leak analyser or soapy water to 

check  all  joints  and  connections  for 
leaks. Tighten or reseal the connection 
where leaks are found. 

Inspecting the equipment 

  Check the condition of the compressor 

air  pump  for  normal  operation  and 
noise levels. 

  Fan  operation  check 

–  the  fans  must 

be 

running 

during 

the 

defined 

compressor work cycles. 

  Check the filter condition 

– clean dirty 

filters or replace with new filters. 

  Check the solenoid valves in the valve 

module. 

  Check  the  operation  of  the  automatic 

condensate drain. 

  Call  in  service  personnel  if  a 

malfunction is suspected. 

18.4.  Inspection of electrical 

connections 

 

Risk of electric shock. 

Inspect  the  product’s  electrical 
connections  when  the  mains 
are disconnected.

 

  Check  the  mechanical  operation  of 

main circuit breaker FA13. 

  Check  the  power  cord,  conductors 

connected to the X1 terminal strip and 
the  main  circuit  breaker  FA13  to 
ensure  they  are  undamaged.  Inspect 
to ensure the connection terminals are 
properly supported to relieve tension. 

  Check 

to 

ensure 

all 

threaded 

conductor terminals are tight (on motor 
circuit  breakers  FA1-6,  contactors 
KM1-6,  etc.).  Tighten  all  loose 
terminals with a screwdriver.  

  Visually  inspect  the  connection  of 

individual  cables  to  the  terminal  strip 
X1  (spring  clips)  and  the  LOGO! 
control system (screw terminals). 

  Inspect  all  screw  terminals  for  the 

protective  green  and  yellow  PE 
grounding 

conductors 

in 

the 

switchboard,  the  motor  section,  the 
cooling  unit  and  the  pressure  vessel. 
Tighten any loose terminals. 

18.5.  Condenste drain 

 

A  wet  floor  resulting  from 
overflow from the vessel poses 
a slip hazard. 

 

Содержание DK50 4x2VT/M

Страница 1: ...DK50 4x2VT M DK50 6x2VT M User manual...

Страница 2: ......

Страница 3: ...K50 6x2VT M EKOM spol s r o Priemyseln 5031 18 SK 921 01 Pie any Slovak Republic tel 421 33 7967255 fax 421 33 7967223 www ekom sk email ekom ekom sk DATE OF LAST REVISION 04 2022 NP DK50 Nx2VTM AD EN...

Страница 4: ...ANTS 9 8 ACCESSORIES 11 9 PRODUCT FUNCTION 12 TECHNICAL DATA 16 INSTALLATION 22 10 INSTALLATION CONDITIONS 22 11 COMPRESSOR ASSEMBLY 23 12 PNEUMATIC CONNECTION 26 13 ELECTRICAL CONNECTION 29 14 COMMIS...

Страница 5: ...mpressed air supplied by the compressor is unsuitable for use with artificial lung ventilation devices without further filtration Any other use of the product beyond its intended use is considered an...

Страница 6: ...FUTURE USE The user manual supports the correct installation operation and maintenance of the product Careful review of this manual will provide the information necessary for the correct operation of...

Страница 7: ...ries and parts mentioned in the technical documentation or expressly approved by the manufacturer should be used The operator must ensure that the device is functioning correctly and safely before eve...

Страница 8: ...for the product If it is necessary to return the product during the warranty period the manufacturer is not liable for damages caused by improper packaging The compressor is shipped in a vertical posi...

Страница 9: ...ufactured according to its intended application in the following variants DK50 4x2VT M Composed of modules 1 compressor module 4x2V air pumps 2 adsorption dryer 3 air tank module 2x110 l DK50 6x2VT M...

Страница 10: ...PRODUCT DESCRIPTION NP DK50 Nx2VTM AD EN 6_04 2022 10 04 2022 DK 50 6x2VT M...

Страница 11: ...specified in the order Type Use Level of filtration m Bypass function Article number FS 40F DK50 4x2VT M DK50 6x2VT M 1 no 604014119 000 FS 40M 1 0 1 604014119 004 FS 40S 1 0 01 604014119 024 FS 40AH...

Страница 12: ...ith the accumulated condensate through the silencer 27 Chamber operation desiccant regeneration is cyclically switched Dry and filtered air then passes through the non return valve into the air tank 2...

Страница 13: ...PRODUCT DESCRIPTION 04 2022 13 NP DK50 Nx2VTM AD EN 6_04 2022 Fig 1 Compressor with adsorption dryer...

Страница 14: ...PRODUCT DESCRIPTION NP DK50 Nx2VTM AD EN 6_04 2022 14 04 2022 Fig 2 Adsorption dryer...

Страница 15: ...e pressure relief valve then closes as the pressure drops Pressure in the compressed air circuit can only increase because of an increase in flow resistance in the compressed air lines or as a result...

Страница 16: ...lectrical feeder mm2 10 Enclosure IP10 Motor power kW 1 2 Air tank volume l 330 Air quality filtration m Maximum operating pressure of safety valve bar 12 0 Noise level at 5 bar LpA dB 73 Operating mo...

Страница 17: ...TECHNICAL DATA 04 2022 17 NP DK50 Nx2VTM AD EN 6_04 2022 Dependence of compressor output on working pressure...

Страница 18: ...operating pressure of safety valve bar 12 0 12 0 Noise at 5 bar LpA dB 72 73 Operating mode S1 100 S1 100 PDP drying performance at 7 bar d C 40 40 Time to fill air tank from 0 to 7 bar s 226 226 Net...

Страница 19: ...ting pressure of safety valve bar 12 0 Noise at 5 bar LpA dB 73 Operating mode S1 100 PDP drying performance at 7 bar d C 20 Time to fill air tank from 0 to 7 bar s 226 Net weight c kg 464 Net dimensi...

Страница 20: ...m operating pressure of safety valve bar 12 0 12 0 Noise at 5 bar LpA dB 72 73 Operating mode S1 100 S1 100 PDP drying performance at 7 bar d C 40 40 Time to fill air tank from 0 to 7 bar s 226 226 Ne...

Страница 21: ...pplies to the following conditions Altitude 0 m n m Temperature 20 C Atmospheric pressure 101325 Pa Relative humidity 0 To calculate FAD compressor capacity in dependence on altitude it is necessary t...

Страница 22: ...iently stable base be aware of the weight of the compressor see the Technical Data chapter The compressor on the operator s side must be at least 70 cm from the wall to allow air flow for cooling purp...

Страница 23: ...releasing the compressor Unpack the compressor compressor modules dryer and air tank from the packaging and remove the transport anchors from the pallet All modules are secured to pallets Use a fork l...

Страница 24: ...INSTALLATION NP DK50 Nx2VTM AD EN 6_04 2022 24 04 2022 Fig 5 Handling the compressor module Fig 6 Levelling the compressor Fig 7 Frame installation...

Страница 25: ...stallation Fig 8 Releasing the air pumps Remove the transport stabilisers from the air pumps X Y Z Fig 8 DK50 4x2VT M 8x mounts DK50 6x2VT M 12x mounts Assembly of the AD dryer Remove the dryer from t...

Страница 26: ...stream or downstream of the cooler is prohibited The temperature of the internal and external parts of the cooler may be hot and reach hazardous temperatures 12 PNEUMATIC CONNECTION Connect the compre...

Страница 27: ...P DK50 Nx2VTM AD EN 6_04 2022 Fig 11 Pneumatic connection AD dryer compressed air inlet Connect the outlet OUT from the compressor s manifold to the inlet AIR IN on the dryer 1 Use the 950 mm hose Fig...

Страница 28: ...t with an operator or other material AD dryer compressed air outlet Connect the outlet AIR OUT from the dryer 1 to the compressor manifold Use the 600 mm hose Fig 13 Compressed air outlet Condensate o...

Страница 29: ...Risk of damage to the device The operator is obliged to provide circuit protection devices for the equipment per the specifications in valid technical standards The product is delivered without a powe...

Страница 30: ...n trays and enclose with a cover Fig 18 Connecting the power cord Connect the TN S mains to the power supply terminal in the equipment s junction box F Connect the electrical components to the mains i...

Страница 31: ...ric shock Ensure the electrical cable does not touch hot parts of the device or connecting hoses 14 COMMISSIONING Make sure all transport stabilizers were removed Check that all compressed air hose co...

Страница 32: ...INSTALLATION NP DK50 Nx2VTM AD EN 6_04 2022 32 04 2022 15 PNEUMATIC DIAGRAMS DK50 4x2VT M...

Страница 33: ...INSTALLATION 04 2022 33 NP DK50 Nx2VTM AD EN 6_04 2022 DK50 6x2VT M...

Страница 34: ...3 Compressor fan 4 Solenoid valve 5 Safety valve 6 Non return valve 7 Relief valve 8 Condensate separator 9 Dryer 10 Pressure switch 11 Pressure gauge 12 Cooler 13 Cooler fan 14 Air tank 15 Condensate...

Страница 35: ...ressor automatically switches off once the pressure in the tank reaches the shut off pressure Potential for damage to pneumatic components The working pressure settings for the pressure switch set by...

Страница 36: ...the cursor control buttons OK and ESC The expansion module has LED indicators for RUN and STOP The parameters of this unit do not require configuration or set up under normal circumstances The LED ind...

Страница 37: ...ntenance service is needed The controller determines an alarm as any situation in which the equipment functionality does not match the standard conditions The individual alarms are indicated by an ala...

Страница 38: ...d for 3 seconds Cancelling this signal also resets the maintenance interval to a value of 2000 Medium priority alarm conditions The equipment is equipped to monitor and signal compressor malfunctions...

Страница 39: ...e Press ESC to show the following menu Use Set to set the current time Press or to move the cursor on the display to Stop and press OK to confirm Never press OK if the cursor is at Set Param Switching...

Страница 40: ...ard maintenance work see Chapter 18 1 may only be performed by the operator s trained personnel Only use manufacturer approved replacement parts and accessories Danger of injury or equipment damage Pr...

Страница 41: ...em parts of the dryer and connecting hoses between the compressor and dryer may be hot do not touch these components Allow the equipment to cool down before maintenance service or connecting disconnec...

Страница 42: ...5 18 4 18 9 18 11 16000 h 12000 h x x x x x x 10000 h x x x x x 8000 h x x x x x 6000 h x x x x 4000 h x x x x x 2000 h x x x x Once every 2 years Once a year Once a week x Once a day x Time interval...

Страница 43: ...x x x x x 4000 h x x x x x x 2000 h x x x x x Once every 2 yeas x Once a year x Once a week Once a day Time interval Relief valve check Checking the operation of temperature sensor switching Check of...

Страница 44: ...equipment Check the condition of the compressor air pump for normal operation and noise levels Fan operation check the fans must be running during the defined compressor work cycles Check the filter...

Страница 45: ...ilter replacement Pull out the rubber plug by hand 2 Remove the dirty intake filter 1 Insert a new filter and replace the rubber plug Pre filter replacement Pull out the pre filter by hand 3 Replace w...

Страница 46: ...7 bar The measured value must be less than the data provided in the Technical Data table 18 9 Check of non return valve operation Compressed air line Check for the proper operation of all non return v...

Страница 47: ...s containing alcohol and chlorides can lead to surface damage and discolouration AD dryer maintenance 18 13 Venting pressure from the dryer The equipment is designed to permit the safe venting of pres...

Страница 48: ...process of manually venting pressure from the equipment is complete after approximately 2 minutes 18 14 Replacement of the dryer s internal filters Working with pressurised pneumatic components poses...

Страница 49: ...eck for any dryer leaks Fig 27 Replacement of internal filters 18 15 Replacement of cassettes with adsorbent media In normal operation the replacement of the cassettes with adsorbent media must be per...

Страница 50: ...zzles 5 and clean as necessary Reverse the procedure to reassemble Check for leaks and the operation of the logic valve and nozzles check for the cyclical switching of the chambers Fig 29 Replacement...

Страница 51: ...e working on the equipment In normal operation the solenoid valves in the bottom of the dryer must be replaced at the defined interval Turn off the compressor Check the pressure in the dryer If the dr...

Страница 52: ...mbled replacement parts The new valve must be assembled before a solenoid valve is replaced Mount the valve coil 4 5 onto the valve body 4 4 and secure with the nut 4 6 Insert the valve membrane sprin...

Страница 53: ...upply and vent all pressure in the equipment to zero The pressure in the compressed air circuit can only increase because of an increase in flow resistance in the compressed air lines or as a result o...

Страница 54: ...ck mains voltage Check the function of the contactor and thermal relays replace if damaged Loose terminals at the motor terminal strip tighten or replace if damaged or broken Motor winding shorted dam...

Страница 55: ...tion system Regeneration solenoid valve not working Check coil operation replace if damaged Air regeneration nozzle plugged Clean or replace the nozzle see product maintenance Cooling fan not working...

Страница 56: ...N If the compressor will not be used for a prolonged time period it is recommended to drain all condensate from the air tank and the condensate separator Then turn on the compressor for 10 minutes kee...

Страница 57: ...y panel alarms operation in alarm conditions Y N N Installation connection to equipment Y Product maintenance maintenance intervals maintenance procedure service intervals operating activities Y N N F...

Страница 58: ......

Страница 59: ......

Страница 60: ...spol s r o Priemyseln 5031 18 921 01 PIE ANY Slovak Republic tel 421 33 7967255 fax 421 33 7967223 e mail ekom ekom sk www ekom sk NP DK50 Nx2VTM AD EN 6_04 2022 112000481 0001 DK50 4x2VT M DK50 6x2V...

Отзывы: