background image

SPARK FAILURE

The gap between the spark electrode and the pilot should be 3.5 - 4.5mm to produce a good spark. There
should be no need to adjust this. If under any circumstances the electric spark fails, the pilot may be lit man-
ually by proceeding with the ignition sequence as previously described, and after turning the control knob
through the spark position, the knob should be held in and the pilot lit with a taper.

SETTING PRESSURE

Remove the screw from the pressure test point. 
The pressure test point is situated on the main injector pipe next to the pilot.
Attach a U gauge. Light the fire on the HIGH setting.

The setting pressure should be in accordance with the figures stated on page 2 of these instructions. The
fire is factory set to achieve these pressures, and any significant variation could indicate a supply problem.

If the pressure is too high, the gas supply meter may be set incorrectly. This should be checked with the fire
running and if necessary reset by the gas supplier.

If the pressure is too low, then check the meter governor pressure with the appliance running. If this is incor-
rect it will need to be reset by the gas supplier. If the setting pressure is too low, but the meter pressure is
acceptable, then a problem in the supply pipework is to be suspected. This will be dirt and debris, kinked
or inadequate size pipes, restriction in a fitting or solder flashing across a joint. (NOTE: you will not get an
accurate reading of the inlet pressure with a pressure gauge on the end of the supply pipe - this is the stat-
ic pressure in the system. You must use a T piece and measure the supply pressure with the fire on High -
the dynamic pressure). Refit and tighten the screw into the pressure test point when the test is complete.

FLUE SPILLAGE MONITORING SYSTEM

This fire is fitted with a flue spillage safety device (ODS). If the fire shuts down during use for no apparent
reason then several things may be suspected. If a door or window has been opened creating a draught, then
pilot disturbance is the problem, and removal of the draught should resolve this. If a grommet seal has been
left out of the firebox then this also will also cause intermittent shutdown. The gas pressure reaching the
fire must also be checked. The thermocouple connection into the back of the gas control valve may also have
worked loose during installation, simply tighten to remedy if this is the case.

If pilot disturbance is not the cause, then the ODS safety system may be in operation. Switch the appliance
OFF, check the flue and carry out any remedial work required. Relight the fire and carry out a spillage test.
DO NOT allow the appliance to be used if it continues to fail a spillage test.
The aeration hole of the pilot must be carefully cleaned out on each annual service to ensure continued func-
tion of the ODS.
The spillage monitoring system shall not be adjusted, modified, or put out of operation by the installer. Any
spare parts fitted MUST be of a type supplied for the purpose by the appliance manufacturer.

If the fire is not spilling, then further guidance should be sought, using the Troubleshooting section as a
guide.

TESTING FOR SPILLAGE

Close all doors and windows to the room containing the appliance. Let the fire run on HIGH for five minutes.
Take a smoke match, light it, and using a smoke match tube, hold it at the top edge of the fire opening,
25mm down and 25mm in. Starting 50mm in from either side, run the smoke match across the opening. All
the smoke should be drawn away up the flue. Any smoke returning into the room indicates that spillage is
occurring. If the initial spillage test fails, run the fire for a further 10 minutes and repeat the test. When the
test has been completed satisfactorily, repeat with any extractor fans in the premises running on the high-
est setting, and any communicating doors open. Finally, repeat with all doors open.

NOTE: If spillage is still indicated after undertaking all of the above, there may be a fault in the flue,
or insufficient ventilation is present.

If the problem cannot be rectified immediately, then expert advice should be sought. Inform the user, dis-
connect the fire, and attach an explanatory label.

9

14.2

14.4

14.3

14.5

©

2009 Focal Point Fires plc.

Содержание eko 2030

Страница 1: ...installation and user instructions All instructions must be handed to user for safekeeping Revision A 06 09 Country s of destination GB IE eko 2030 fuel effect gas fire...

Страница 2: ...Eko 2030...

Страница 3: ...nd only used in a sufficiently ventilated space The appliance is designed for installation on to a non combustible hearth of at least 300mm depth This appliance is factory set for operation on the gas...

Страница 4: ...ce must be installed in accordance with the rules in force and used only in a suf ficiently ventilated space This appliance is intended for decorative purposes Consult all instructions before installa...

Страница 5: ...re must be no opening in the flue apart from the one that the appli ance is installed into and the one venting the gases into the air A suitable terminal may be fitted such as class GC1 as regulations...

Страница 6: ...fire providing that it complies with the dimensions given below A non combustible shelf may be fitted to within 10mm of the top edge of the fireframe Combustible mate rials such as wood may be fitted...

Страница 7: ...is appliance can be fitted into a number of proprietory flue boxes provided that the minimum dimensions given in the diagram below are complied with The flue outlet of the fire must not obscure the fl...

Страница 8: ...afely to one side Firstly remove the stainless steel shelf from the fire box in order to access the burner This is achieved by removal of the two retaining screws located under the shelf at either sid...

Страница 9: ...base and the relevant points in the opening or on the wall Rawlplugs will again be required Pre punched holes are not provided for this purpose to allow you to choose the optimum positions Do not scre...

Страница 10: ...itioned as close to the correct layout as possible Before finally fitting cables ensure the self adhesive sealing strips are in position on the back of the appliance frame The fireframe must be sealed...

Страница 11: ...the need arise see the later Servicing section of these instructions TESTING AND COMMISSIONING Turn on and test the gas supply up to the fire for any leaks in accordance with current edition of BS6891...

Страница 12: ...rbance is the problem and removal of the draught should resolve this If a grommet seal has been left out of the firebox then this also will also cause intermittent shutdown The gas pressure reaching t...

Страница 13: ...curing the tray to the firebox 5 Lift the burner tray from the firebox 6 Remove the firebox as detailed in the relevant section 7 Check the area behind the firebox for rubble accumulation and remove I...

Страница 14: ...e the tray as previously described The pilot unit can be removed by undoing the tubing nut the ther mocouple nut on the rear of the valve lint arrestor two securing screws and lifting away Remove the...

Страница 15: ...and then cuts off Excessive room draught or flue pull rectify Loose or faulty thermocouple rectify ODS system in operation Firebox grommet seal not fitted rectify Lint in pilot aeration hole clean th...

Страница 16: ...ude onto the hearth DO NOT burn any foreign material on this fire the fuel effect must be of the correct type and laid out in accordance with the relevant section of these instructions Failure to do s...

Страница 17: ...required see IS 813 ICP3 IS 327 and any other rules in force FUEL BED LAYOUT The appliance is supplied with 13 indi vidually wrapped hand finished ceramic pebbles and 1 combustion matrix 1 Remove the...

Страница 18: ...t on 6 Place the pebble E onto the peg E on the matrix as shown 7 Place the pebble F onto the peg F on the matrix as shown The pebble should be orientated so it sits slightly over the hole in the comb...

Страница 19: ...tion procedure To achieve the HIGH setting push the control knob in slightly and con tinue turning anti clockwise to the high position The main burner should light after a few seconds To decrease the...

Страница 20: ...d completely cold PAINTED AREAS These can be cleaned using a dry cloth PEBBLES AND CERAMICS Remove the ceramic components Gently clean with a soft brush in the open air Do not create dust from the peb...

Отзывы: