• Do not locate in
insect infested areas
. Small insects getting into the optical sensor chamber can
cause intermittent alarms. Insects and contamination on the heat sensor can increase its
response time.
4. Installation
The Alarm is designed to be permanently mounted, using it’s own built-in terminal
block to connect it to the mains. The mounting plate can be screwed directly to the
ceiling. Alternatively it can be screwed to a standard junction box. It requires a current
of 60mA. The Alarm must not be exposed to dripping or splashing. There are important
markings on the underside of the Alarm.
Caution
Alternative Energy Sources
- (Wind, Solar, UPS etc.)
This product is designed to be connected to a Pure or True Sine Wave 230 Vac supply.
If connecting to a power source that utilises an inverter, e.g. PV solar panel, the Total
Harmonic Distortion (THD) must be less than 5%. If in doubt please check with the
manufacturer of the inverter.
This also applies to battery powered UPS (Uninterruptible Power Supply) inverters.
Light Dimmer Circuits
– The Alarms
must not
be powered from a light dimmer circuit.
IMPORTANT PRECAUTION:
Do not install Alarms in new or renovated buildings
until all work is completed (including floor coverings) and the building has been
fully cleaned. The wiring can be installed when appropriate.
(Excessive dust and
debris from building work can contaminate the optical sensor chamber or heat
sensor and cause problems. It will also invalidate the guarantee)
. If it must be
13