Chapter 4: Testing and troubleshooting
56
SIGA-REL Technical Reference Manual
Device
Condition
LED
2-LCD message
Open
Trouble
Open Fault
Release_2 [1]
[1] Message requires user programming
SIGA-REL fault messages on EST3 panels
WARNING:
Disconnect all wiring on TB4 of the SIGA-REL (release circuits 1 and
2) when servicing the system. Disabling points does not prevent activation of the
release circuits. Failure to follow these instructions may result in loss of life,
serious injury, or property damage.
When programming is complete, the fire alarm control panel resets itself,
reconstruct the line data card, and map it. Upon reset, device supervision may
cause the panel to generate a common trouble active for each SIGA-REL circuit.
This is a normal indication, and it should go away within minutes. Table 22 lists
the indications you may see for the SIGA-REL on the 3-LCD.
Table 22: SIGA-REL fault messages
Device
Condition
LED
3-LCD message
Abort
Short
Monitor
MONITOR ACT (Abort)
Open
Trouble
COMMON TRBL ACT
Abort [1]
Expanded message: TROUBLE OPEN ACT
Manual
Short
Alarm
PULL STATION ACT
Manual [1]
Expanded message: TROUBLE SHRT ACT
Open
Trouble
COMMON TRBL ACT
Manual [1]
Expanded message: TROUBLE OPEN ACT
Prerelease_1
Short
Trouble
COMMON TRBL ACT
Prerelease_1 [1]
Expanded message: TROUBLE SHRT ACT
Open
Trouble
COMMON TRBL ACT
Prerelease_1 [1]
Expanded message: TROUBLE OPEN ACT
Prerelease_2
Short
Trouble
COMMON TRBL ACT
Prerelease_2 [1]
Expanded message: TROUBLE SHRT ACT