![Edwards SIGA-REL Technical Скачать руководство пользователя страница 43](http://html1.mh-extra.com/html/edwards/siga-rel-technical/siga-rel-technical_reference-manual_2366019043.webp)
Chapter 3: Programming
SIGA-REL Technical Reference Manual
35
Programming the SIGA-REL in the 2-SDU
Adding the SIGA-REL to the database
WARNING:
This information was prepared for users who are proficient in every
aspect of 2-SDU programming. Do not attempt to program the SIGA-REL if your
certification is not current. Incorrect programming may result in loss of life,
serious injury, or property damage.
The SIGA-REL is a single module with six serial numbers. Addresses will differ
for each installation, but they must be consecutive.
Note:
If you are adding other Signature Series devices to the project database,
add the SIGA-REL last. Adding devices after the SIGA-REL may disrupt the
addressing scheme.
The SIGA-REL has six addressable circuits. To add the SIGA-REL to the project
database, you must add three SIGA-REL modules. The first SIGA-REL is for the
abort switch and manual release switch circuits, the second for the two release
circuits, and the third for the two prerelease circuits.
Note:
You cannot have more than 10 SIGA-REL modules on one Signature loop.
The SIGA-REL provides only one serial number label. When you scan in the
SIGA-REL, only the first two serial numbers appear in the database.
Caution:
Do not use the Accept Actual function in the Signature Mapping tool.
Accepted data may corrupt the database by causing it to see every device as two
devices.
To add the SIGA-REL to the database:
1. Use the SDC Configuration dialog box to add three SIGA-REL modules:
Device type = Monitor
Model = SIGA-REL
Personality code = 3
Quantity = 3
2. Scan or enter the SIGA-REL serial number label in the first address slot.
3. Complete each SIGA-REL address as shown in Table 16
. You don’t need to
enter serial numbers for all addresses. This happens in a later step.
4. Use the Object Configuration dialog box to assign labels and messages to
each SIGA-REL address, as shown in Table 17.