Chapter 3: Programming
48
SIGA-REL Technical Reference Manual
Text 2: DISCONNECT SW
No further programming is necessary.
Step 9: Indicate active prerelease and release circuits
Two PAM-1 control relays and a SIGA-CT2 module are used to indicate
activation of the prerelease and release relays.
Install and wire the components according to Figure 14. In this case, the 1st
Device represents terminals 7 and 8, the release relay. The 2nd Device
represents terminals 5 and 6, the prerelease relay.
Configure the SIGA-CT2 module as follows:
1st Device represents
1st Device Type: Monitor
1st Personality:(3) Active B
1st Text 1: REL1_RELEASE
1st Text 2: CKT_ACTIVE
2nd Device Type: Monitor
2nd Personality:(3) Active B
2nd Text 1: REL1_PREREL
2nd Text 2: CKT_ACTIVE
When a circuit is activated, the SIGA-CT2 module activates a monitor event. The
corresponding event message identifies which circuit was activated. No further
programming is necessary.
Step 10: Create a drill prerelease response
Here, you create a response that activates the prerelease circuits when someone
presses the Drill switch.
Note:
Create this response only if required. Pressing Drill will activate the
prerelease circuits, but pressing Drill a second time will not restore the
prerelease circuits. You must press Reset to silence the prerelease circuits.
1. Click Configure > Correlations.
2. Click the Devices tab, and then select the Show Pseudo Points check box.
3. Select the circuit labeled Drill (address 007).
4. Click the Responses tab, click the Response Type arrow, and then select
Active.