Chapter 3: Programming
SIGA-REL Technical Reference Manual
47
4. Select only the detectors required to activate the SIGA-REL release circuits
then click OK.
5. Click the Responses tab, click the Response Type arrow, and then select
Active.
6. Click Delays.
7. In the Delay On list, click Activation and Restoration.
8. Set the Seconds box to 10.
9. Click Outputs, select the device labeled SIGA-REL1 A003 RELEASE 1 & 2,
and then click OK.
Step 7: Create a manual release response
In this step, you create a manual release response that activates the release
circuits when someone presses the manual release switch. Add the prerelease
response, create the delay, and then add the release response in that order.
1. Click the Devices tab, and then select the circuit labeled SIGA-REL A002
MAN RELEASE.
2. Click the Responses tab, click the Response Type arrow, and then select
Active.
3. Click Outputs, select the device labeled SIGA-REL1 A005 PRERELEASE 1 &
2, and then click OK.
4. Click Delays and set the delay options as follows:
Delay On: Activation and Restoration
Seconds: 0
5. Click Outputs, select the device labeled SIGA-REL1 A003 RELEASE 1 & 2,
and then click OK.
Note:
The delay is required so that the prerelease and release responses occur
in the correct order. Prerelease must come before release.
Step 8: Supervise the service disconnect switch
If your application requires supervision of the service disconnect station, install
and wire components according to Figure 13. A SIGA-CT1 module supervises
the RELA-SRV-1 switch. Configure the SIGA-CT1 as follows:
Device Type: Supervisory
Personality: (3) Active B
Text 1: SIGA-REL1 RELEASE 1